BE-2x280CD5-B01C C
370.65 kW
Defrost: None
Product code: BE-580AC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 106,403 m³/h |
|---|---|
| External surface | 1,591.9 m² |
| Inner volume | 229.1 dm³ |
| Fin material | Aluminium |
| Net weight | 1,466 kg |
| Quantity | 5 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 9,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-580AC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 216.04 | not rated | not rated | not rated | not rated | not rated |
| 40 | 370.46 | 216.62 | not rated | not rated | not rated | not rated |
| 45 | 520.57 | 369.64 | 217.07 | not rated | not rated | not rated |
| 50 | 669.21 | 518.46 | 368.88 | 217.49 | not rated | not rated |
| 55 | 817.22 | 665.99 | 516.68 | 368.35 | 217.98 | not rated |
| 60 | 964.90 | 812.92 | 663.22 | 515.28 | 368.02 | 218.58 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 171.59 | not rated | not rated | not rated | not rated | not rated |
| 40 | 291.53 | 171.99 | not rated | not rated | not rated | not rated |
| 45 | 407.71 | 290.72 | 172.30 | not rated | not rated | not rated |
| 50 | 522.66 | 405.89 | 290.00 | 172.60 | not rated | not rated |
| 55 | 637.03 | 519.88 | 404.31 | 289.48 | 172.96 | not rated |
| 60 | 751.08 | 633.33 | 517.49 | 403.08 | 289.22 | 173.45 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 370.463 | 64.29 | 27.7 |
| Low speed (Y) | 291.534 | 50.56 | 18.0 |
| A | 1808 mm |
|---|---|
| B | 1150 mm |
| C | 6460 mm |
| F | 1050 mm |
| G | 7060 mm |
| E1 | 1230 mm |
| E2 | 1200 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 7060 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.