Skip to Content

Dry cooler BE-580BB1-B01 C

Dry cooler BE-580BB1-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-580BB1-B01 C

Heat rejection i
320.62 kW
Air flow
106,959 m³/h
Fans
5 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 106,959 m³/h
External surface 969.5 m²
Inner volume 119.4 dm³
Fin materialAluminium
Net weight 1,241 kg
Fans
Quantity 5
Diameter 800 mm
Speed 900 rpm
Power 9,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 55.0 dB(A)
Sound power 87.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-580BB1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
320.615 kW Fluid flow 55.64 m³/h Pressure drop 79.1 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
255.219 kW Fluid flow 44.29 m³/h Pressure drop 52.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 186.70 not rated not rated not rated not rated not rated
40 320.62 187.11 not rated not rated not rated not rated
45 451.52 320.09 187.43 not rated not rated not rated
50 581.47 450.18 319.65 187.74 not rated not rated
55 710.96 579.34 449.02 319.32 188.09 not rated
60 840.23 708.06 577.48 448.11 319.19 188.53

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 149.66 not rated not rated not rated not rated not rated
40 255.22 149.93 not rated not rated not rated not rated
45 358.16 254.70 150.16 not rated not rated not rated
50 460.26 356.95 254.24 150.37 not rated not rated
55 561.97 458.38 355.88 253.91 150.64 not rated
60 663.47 559.44 456.73 355.06 253.76 150.99

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 320.615 55.64 79.1
Low speed (Y) 255.219 44.29 52.7

Dimensions

Dimension drawing of BE-580BB1-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 5960 mm
F 1050 mm
G 6560 mm
E1 1130 mm
E2 1100 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 6560 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.