Dry cooler BE-580EC5-B01 C

Dry cooler BE-580EC5-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-580EC5-B01 C

Heat rejection i
390.40 kW
Air flow
104,167 m³/h
Fans
5 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • D
    Number of fans per row: 5 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): C — 4 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 01 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)

Data

Coil
Air flow 104,167 m³/h
External surface 1,514.1 m²
Inner volume 339.5 dm³
Fin materialAluminium
Net weight 1,524 kg
Fans
Quantity 5
Diameter 800 mm
Speed 900 rpm
Power 9,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 55.0 dB(A)
Sound power 87.0 dB(A)
Energy class D
Connections
Inlet 3"
Outlet 3"
Defrost
BE-580EC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
390.399 kW Fluid flow 67.71 m³/h Pressure drop 63.1 kPa
Heat rejection · Low speed (Y)
302.630 kW Fluid flow 52.49 m³/h Pressure drop 40.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 233.99 not rated not rated not rated not rated not rated
40 390.40 233.80 not rated not rated not rated not rated
45 542.86 388.91 233.60 not rated not rated not rated
50 694.00 540.21 387.65 233.52 not rated not rated
55 844.53 690.22 537.95 386.67 233.59 not rated
60 994.72 839.63 686.98 536.16 386.11 233.89

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 183.11 not rated not rated not rated not rated not rated
40 302.63 182.90 not rated not rated not rated not rated
45 418.89 301.38 182.66 not rated not rated not rated
50 534.06 416.70 300.31 182.56 not rated not rated
55 648.73 530.98 414.85 299.51 182.62 not rated
60 763.12 644.76 528.35 413.42 299.07 182.82

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 390.399 67.71 63.1
Low speed (Y) 302.630 52.49 40.1

Dimensions

Dimension drawing of BE-580EC5-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 6460 mm
F 1050 mm
G 7060 mm
E1 1230 mm
E2 1200 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 7060 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.