Skip to Content

Dry cooler BE-680AD1-B01 C

Dry cooler BE-680AD1-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-680AD1-B01 C

Heat rejection i
518.74 kW
Air flow
123,601 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • D
    Number of fans per row: 6 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): D — 5 tube rows
  • H
    Fin spacing: 1 — 2.1 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 01 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)

Data

Coil
Air flow 123,601 m³/h
External surface 2,823.4 m²
Inner volume 324.5 dm³
Fin materialAluminium
Net weight 1,945 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 88.0 dB(A)
Energy class D
Connections
Inlet 3"
Outlet 3"
Defrost
BE-680AD1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
518.736 kW Fluid flow 89.96 m³/h Pressure drop 111.1 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
394.818 kW Fluid flow 68.48 m³/h Pressure drop 68.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 317.15 not rated not rated not rated not rated not rated
40 518.74 316.27 not rated not rated not rated not rated
45 714.70 515.96 315.52 not rated not rated not rated
50 908.79 710.17 513.57 314.97 not rated not rated
55 1102.03 902.58 706.28 511.71 314.72 not rated
60 1294.79 1094.15 897.24 703.20 510.51 314.90

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 244.05 not rated not rated not rated not rated not rated
40 394.82 243.29 not rated not rated not rated not rated
45 541.11 392.56 242.64 not rated not rated not rated
50 685.95 537.51 390.65 242.18 not rated not rated
55 830.13 681.07 534.46 389.18 242.01 not rated
60 973.95 823.98 676.92 532.09 388.29 242.19

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 518.736 89.96 111.1
Low speed (Y) 394.818 68.48 68.4

Dimensions

Dimension drawing of BE-680AD1-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 7660 mm
F 1050 mm
G 8260 mm
E1 1230 mm
E2 1200 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 8260 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.