Skip to Content

Dry cooler BE-780EC5-B01 C

Dry cooler BE-780EC5-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-780EC5-B01 C

Heat rejection i
547.25 kW
Air flow
145,834 m³/h
Fans
7 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 145,834 m³/h
External surface 2,117.9 m²
Inner volume 478.8 dm³
Fin materialAluminium
Net weight 2,097 kg
Fans
Quantity 7
Diameter 800 mm
Speed 900 rpm
Power 12,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 88.5 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-780EC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
547.254 kW Fluid flow 94.92 m³/h Pressure drop 70.1 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
424.188 kW Fluid flow 73.57 m³/h Pressure drop 44.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 328.49 not rated not rated not rated not rated not rated
40 547.25 328.12 not rated not rated not rated not rated
45 760.58 545.14 327.79 not rated not rated not rated
50 972.09 756.83 543.31 327.62 not rated not rated
55 1182.74 966.75 753.63 541.90 327.67 not rated
60 1392.93 1175.86 962.19 751.09 541.08 328.07

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 257.03 not rated not rated not rated not rated not rated
40 424.19 256.63 not rated not rated not rated not rated
45 586.86 422.39 256.28 not rated not rated not rated
50 748.03 583.77 420.87 256.10 not rated not rated
55 908.51 743.69 581.14 419.73 256.15 not rated
60 1068.60 902.93 739.99 579.12 419.08 256.41

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 547.254 94.92 70.1
Low speed (Y) 424.188 73.57 44.7

Dimensions

Dimension drawing of BE-780EC5-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1300 mm
C 8860 mm
F 1150 mm
G 9460 mm
E1 1230 mm
E2 1200 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 9460 mm
Width 1300 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.