Skip to Content

Dry cooler BE-791AC5-B04 C

Dry cooler BE-791AC5-B04 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-791AC5-B04 C

Heat rejection i
638.61 kW
Air flow
193,875 m³/h
Fans
7 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 193,875 m³/h
External surface 2,228.6 m²
Inner volume 330.9 dm³
Fin materialAluminium
Net weight 2,057 kg
Fans
Quantity 7
Diameter 910 mm
Speed 840 rpm
Power 19,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 66.0 dB(A)
Sound power 98.5 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BE-791AC5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
638.612 kW Fluid flow 110.83 m³/h Pressure drop 85.4 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
511.213 kW Fluid flow 88.72 m³/h Pressure drop 57.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 375.88 not rated not rated not rated not rated not rated
40 638.61 376.24 not rated not rated not rated not rated
45 895.31 637.09 376.50 not rated not rated not rated
50 1149.97 892.07 635.80 376.82 not rated not rated
55 1403.73 1145.10 889.29 634.83 377.30 not rated
60 1656.98 1397.23 1140.91 887.15 634.37 378.08

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 303.54 not rated not rated not rated not rated not rated
40 511.21 303.72 not rated not rated not rated not rated
45 713.58 509.80 303.85 not rated not rated not rated
50 914.25 710.71 508.60 304.05 not rated not rated
55 1114.12 910.02 708.30 507.66 304.45 not rated
60 1313.54 1108.53 906.42 706.46 507.30 305.08

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 638.612 110.83 85.4
Low speed (Y) 511.213 88.72 57.5

Dimensions

Dimension drawing of BE-791AC5-B04 C
Dimension drawing
Dimensions as drawn
A 1958 mm
B 1300 mm
C 8860 mm
F 1150 mm
G 9460 mm
E1 1230 mm
E2 1200 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 9460 mm
Width 1300 mm
Height 1958 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.