BE-t-2x580GB1-B01C C
697.84 kW
Defrost: None
Product code: BE-791AD5-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 189,424 m³/h |
|---|---|
| External surface | 2,785.8 m² |
| Inner volume | 399.0 dm³ |
| Fin material | Aluminium |
| Net weight | 2,220 kg |
| Quantity | 7 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 19,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 66.0 dB(A) |
|---|---|
| Sound power | 98.5 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-791AD5-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 415.83 | not rated | not rated | not rated | not rated | not rated |
| 40 | 698.36 | 415.85 | not rated | not rated | not rated | not rated |
| 45 | 973.48 | 696.01 | 415.89 | not rated | not rated | not rated |
| 50 | 1246.24 | 969.15 | 694.08 | 416.00 | not rated | not rated |
| 55 | 1517.87 | 1239.90 | 965.43 | 692.66 | 416.40 | not rated |
| 60 | 1788.87 | 1509.57 | 1234.47 | 962.58 | 691.88 | 417.17 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 328.84 | not rated | not rated | not rated | not rated | not rated |
| 40 | 546.67 | 328.84 | not rated | not rated | not rated | not rated |
| 45 | 758.35 | 544.85 | 328.88 | not rated | not rated | not rated |
| 50 | 967.97 | 754.92 | 543.35 | 328.94 | not rated | not rated |
| 55 | 1176.64 | 963.00 | 752.06 | 542.30 | 329.36 | not rated |
| 60 | 1384.78 | 1170.16 | 958.84 | 749.95 | 541.87 | 330.11 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 698.357 | 121.20 | 69.7 |
| Low speed (Y) | 546.674 | 94.82 | 45.0 |
| A | 1958 mm |
|---|---|
| B | 1300 mm |
| C | 8860 mm |
| F | 1150 mm |
| G | 9460 mm |
| E1 | 1230 mm |
| E2 | 1200 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 9460 mm |
|---|---|
| Width | 1300 mm |
| Height | 1958 mm |
Our engineers answer with a selection for your conditions.