Dry cooler BE-t-280HB5-B01 C

Dry cooler BE-t-280HB5-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-280HB5-B01 C

Heat rejection i
171.82 kW
Air flow
44,472 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 44,472 m³/h
External surface 537.1 m²
Inner volume 75.2 dm³
Fin materialAluminium
Net weight 666 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 51.0 dB(A)
Sound power 83.0 dB(A)
Energy class D
Connections
Inlet 2"
Outlet 2"
Defrost
BE-t-280HB5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
171.821 kW Fluid flow 29.80 m³/h Pressure drop 99.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
134.234 kW Fluid flow 23.28 m³/h Pressure drop 64.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 103.53 not rated not rated not rated not rated not rated
40 171.82 103.30 not rated not rated not rated not rated
45 238.34 170.93 103.08 not rated not rated not rated
50 304.25 236.85 170.15 102.91 not rated not rated
55 369.89 302.18 235.53 169.50 102.79 not rated
60 435.38 367.24 300.35 234.44 169.03 102.79

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 81.61 not rated not rated not rated not rated not rated
40 134.23 81.37 not rated not rated not rated not rated
45 185.36 133.45 81.16 not rated not rated not rated
50 236.00 184.08 132.75 80.98 not rated not rated
55 286.41 234.23 182.95 132.18 80.88 not rated
60 336.70 284.17 232.68 182.02 131.77 80.87

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 171.821 29.80 99.2
Low speed (Y) 134.234 23.28 64.0

Dimensions

Dimension drawing of BE-t-280HB5-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 4060 mm
F 1050 mm
G 4660 mm
E1 1830 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 4660 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.