BE-280DC1-B01 C
172.05 kW
Defrost: None
Product code: BE-t-280HB5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 44,472 m³/h |
|---|---|
| External surface | 537.1 m² |
| Inner volume | 75.2 dm³ |
| Fin material | Aluminium |
| Net weight | 666 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-t-280HB5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 103.53 | not rated | not rated | not rated | not rated | not rated |
| 40 | 171.82 | 103.30 | not rated | not rated | not rated | not rated |
| 45 | 238.34 | 170.93 | 103.08 | not rated | not rated | not rated |
| 50 | 304.25 | 236.85 | 170.15 | 102.91 | not rated | not rated |
| 55 | 369.89 | 302.18 | 235.53 | 169.50 | 102.79 | not rated |
| 60 | 435.38 | 367.24 | 300.35 | 234.44 | 169.03 | 102.79 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 81.61 | not rated | not rated | not rated | not rated | not rated |
| 40 | 134.23 | 81.37 | not rated | not rated | not rated | not rated |
| 45 | 185.36 | 133.45 | 81.16 | not rated | not rated | not rated |
| 50 | 236.00 | 184.08 | 132.75 | 80.98 | not rated | not rated |
| 55 | 286.41 | 234.23 | 182.95 | 132.18 | 80.88 | not rated |
| 60 | 336.70 | 284.17 | 232.68 | 182.02 | 131.77 | 80.87 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 171.821 | 29.80 | 99.2 |
| Low speed (Y) | 134.234 | 23.28 | 64.0 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 4060 mm |
| F | 1050 mm |
| G | 4660 mm |
| E1 | 1830 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 4660 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.