Dry cooler BE-t-2x180HC5-B01C C

Dry cooler BE-t-2x180HC5-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-2x180HC5-B01C C

Heat rejection i
176.93 kW
Air flow
42,795 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 42,795 m³/h
External surface 553.8 m²
Inner volume 82.3 dm³
Fin materialAluminium
Net weight 854 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 51.0 dB(A)
Sound power 83.0 dB(A)
Energy class D
Connections
Inlet 2"
Outlet 2"
Defrost
BE-t-2x180HC5-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
176.933 kW Fluid flow 30.68 m³/h Pressure drop 54.5 kPa
Heat rejection · Low speed (Y)
135.857 kW Fluid flow 23.56 m³/h Pressure drop 34.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 106.73 not rated not rated not rated not rated not rated
40 176.93 106.59 not rated not rated not rated not rated
45 244.92 176.03 106.46 not rated not rated not rated
50 312.16 243.34 175.23 106.37 not rated not rated
55 379.07 309.94 241.95 174.60 106.35 not rated
60 445.79 376.22 308.00 240.83 174.17 106.45

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 82.81 not rated not rated not rated not rated not rated
40 135.86 82.67 not rated not rated not rated not rated
45 187.06 135.08 82.53 not rated not rated not rated
50 237.67 185.75 134.40 82.43 not rated not rated
55 288.01 235.86 184.61 133.86 82.40 not rated
60 338.20 285.70 234.28 183.69 133.50 82.47

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 176.933 30.68 54.5
Low speed (Y) 135.857 23.56 34.0

Dimensions

Dimension drawing of BE-t-2x180HC5-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 2250 mm
F 2230 mm
G 2850 mm
E1 1850 mm
H 2500 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 2850 mm
Width 2300 mm
Height 2453 mm

Downloads