BE-t-2x291GC5-C04C C
356.47 kW
Defrost: None
Product code: BE-t-2x280HB1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 87,982 m³/h |
|---|---|
| External surface | 1,162.7 m² |
| Inner volume | 152.7 dm³ |
| Fin material | Aluminium |
| Net weight | 1,527 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-t-2x280HB1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 213.95 | not rated | not rated | not rated | not rated | not rated |
| 40 | 356.12 | 213.62 | not rated | not rated | not rated | not rated |
| 45 | 493.97 | 354.30 | 213.35 | not rated | not rated | not rated |
| 50 | 630.38 | 490.77 | 352.68 | 213.15 | not rated | not rated |
| 55 | 766.11 | 625.86 | 487.96 | 351.36 | 213.08 | not rated |
| 60 | 901.46 | 760.30 | 621.89 | 485.64 | 350.45 | 213.25 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 167.24 | not rated | not rated | not rated | not rated | not rated |
| 40 | 275.65 | 166.94 | not rated | not rated | not rated | not rated |
| 45 | 380.41 | 274.05 | 166.64 | not rated | not rated | not rated |
| 50 | 483.98 | 377.69 | 272.64 | 166.40 | not rated | not rated |
| 55 | 587.01 | 480.20 | 375.31 | 271.49 | 166.30 | not rated |
| 60 | 689.73 | 582.19 | 476.90 | 373.36 | 270.68 | 166.41 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 356.117 | 61.76 | 62.2 |
| Low speed (Y) | 275.653 | 47.81 | 39.3 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 4050 mm |
| F | 2330 mm |
| G | 4650 mm |
| E1 | 1850 mm |
| H | 4300 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 4650 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.