BE-2x291AC1-C04C C
338.92 kW
Defrost: None
Product code: BE-t-2x291GB1-C04C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 104,443 m³/h |
|---|---|
| External surface | 633.8 m² |
| Inner volume | 94.9 dm³ |
| Fin material | Aluminium |
| Net weight | 1,175 kg |
| Quantity | 4 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 11,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 96.4 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-t-2x291GB1-C04C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 197.11 | not rated | not rated | not rated | not rated | not rated |
| 40 | 339.08 | 197.74 | not rated | not rated | not rated | not rated |
| 45 | 477.66 | 338.77 | 198.30 | not rated | not rated | not rated |
| 50 | 615.13 | 476.52 | 338.54 | 198.84 | not rated | not rated |
| 55 | 752.08 | 613.18 | 475.58 | 338.49 | 199.46 | not rated |
| 60 | 888.73 | 749.33 | 611.54 | 474.94 | 338.66 | 200.18 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 157.31 | not rated | not rated | not rated | not rated | not rated |
| 40 | 267.93 | 157.78 | not rated | not rated | not rated | not rated |
| 45 | 375.54 | 267.64 | 158.23 | not rated | not rated | not rated |
| 50 | 482.21 | 374.57 | 267.43 | 158.68 | not rated | not rated |
| 55 | 588.41 | 480.59 | 373.81 | 267.36 | 159.19 | not rated |
| 60 | 694.35 | 586.17 | 479.30 | 373.35 | 267.56 | 159.84 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 339.082 | 58.85 | 113.8 |
| Low speed (Y) | 267.928 | 46.50 | 74.9 |
| A | 2511 mm |
|---|---|
| B | 2300 mm |
| C | 2850 mm |
| F | 2230 mm |
| G | 3450 mm |
| E1 | 1250 mm |
| H | 3100 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 2850 mm |
|---|---|
| Width | 2300 mm |
| Height | 2511 mm |
Our engineers answer with a selection for your conditions.