BE-2x291CC5-B04T C
448.77 kW
Defrost: None
Product code: BE-t-2x380GB1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 124,147 m³/h |
|---|---|
| External surface | 1,065.8 m² |
| Inner volume | 157.8 dm³ |
| Fin material | Aluminium |
| Net weight | 1,725 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-t-2x380GB1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 264.03 | not rated | not rated | not rated | not rated | not rated |
| 40 | 448.47 | 264.46 | not rated | not rated | not rated | not rated |
| 45 | 627.84 | 447.31 | 264.79 | not rated | not rated | not rated |
| 50 | 805.62 | 625.31 | 446.26 | 265.14 | not rated | not rated |
| 55 | 982.62 | 801.75 | 623.14 | 445.56 | 265.63 | not rated |
| 60 | 1159.18 | 977.46 | 798.44 | 621.46 | 445.26 | 266.30 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 208.29 | not rated | not rated | not rated | not rated | not rated |
| 40 | 350.11 | 208.54 | not rated | not rated | not rated | not rated |
| 45 | 487.71 | 349.07 | 208.76 | not rated | not rated | not rated |
| 50 | 623.88 | 485.54 | 348.19 | 208.99 | not rated | not rated |
| 55 | 759.39 | 620.64 | 483.71 | 347.57 | 209.32 | not rated |
| 60 | 894.52 | 755.11 | 617.90 | 482.33 | 347.32 | 209.89 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 448.471 | 77.84 | 79.7 |
| Low speed (Y) | 350.108 | 60.71 | 51.2 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 3750 mm |
| F | 2330 mm |
| G | 4350 mm |
| E1 | 1150 mm |
| E2 | 1100 mm |
| H | 4000 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4350 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.