BE-2x280CD5-B01T C
383.15 kW
Defrost: None
Product code: BE-t-2x380GB5-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 121,596 m³/h |
|---|---|
| External surface | 762.0 m² |
| Inner volume | 134.3 dm³ |
| Fin material | Aluminium |
| Net weight | 1,511 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-t-2x380GB5-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 222.49 | not rated | not rated | not rated | not rated | not rated |
| 40 | 382.79 | 223.15 | not rated | not rated | not rated | not rated |
| 45 | 539.32 | 382.36 | 223.71 | not rated | not rated | not rated |
| 50 | 694.65 | 537.94 | 382.02 | 224.27 | not rated | not rated |
| 55 | 849.39 | 692.33 | 536.78 | 381.85 | 224.87 | not rated |
| 60 | 1003.81 | 846.17 | 690.39 | 535.97 | 381.94 | 225.62 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 177.67 | not rated | not rated | not rated | not rated | not rated |
| 40 | 302.94 | 178.15 | not rated | not rated | not rated | not rated |
| 45 | 424.91 | 302.50 | 178.57 | not rated | not rated | not rated |
| 50 | 545.78 | 423.69 | 302.17 | 179.00 | not rated | not rated |
| 55 | 666.18 | 543.79 | 422.64 | 302.01 | 179.51 | not rated |
| 60 | 786.29 | 663.45 | 542.14 | 421.95 | 302.09 | 180.13 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 382.787 | 66.44 | 78.7 |
| Low speed (Y) | 302.936 | 52.58 | 51.9 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 3750 mm |
| F | 2230 mm |
| G | 4350 mm |
| E1 | 1150 mm |
| E2 | 1100 mm |
| H | 4000 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4350 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.