Skip to Content

Dry cooler BE-t-2x391GB5-C04C C

Dry cooler BE-t-2x391GB5-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-2x391GB5-C04C C

Heat rejection i
455.09 kW
Air flow
159,133 m³/h
Fans
6 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 159,133 m³/h
External surface 805.7 m²
Inner volume 138.0 dm³
Fin materialAluminium
Net weight 1,593 kg
Fans
Quantity 6
Diameter 910 mm
Speed 840 rpm
Power 16,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 66.0 dB(A)
Sound power 98.2 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BE-t-2x391GB5-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
455.091 kW Fluid flow 78.99 m³/h Pressure drop 45.4 kPa
Heat rejection · Low speed (Y)
365.307 kW Fluid flow 63.39 m³/h Pressure drop 30.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 257.64 not rated not rated not rated not rated not rated
40 455.09 259.40 not rated not rated not rated not rated
45 647.84 455.52 260.93 not rated not rated not rated
50 839.09 647.16 455.93 262.29 not rated not rated
55 1029.67 837.38 646.63 456.44 263.62 not rated
60 1219.84 1026.93 835.97 646.40 457.17 265.01

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 208.53 not rated not rated not rated not rated not rated
40 365.31 209.97 not rated not rated not rated not rated
45 517.78 365.61 211.23 not rated not rated not rated
50 668.86 517.14 365.92 212.37 not rated not rated
55 819.30 667.36 516.68 366.34 213.51 not rated
60 969.36 816.98 666.21 516.54 367.01 214.72

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 455.091 78.99 45.4
Low speed (Y) 365.307 63.39 30.6

Dimensions

Dimension drawing of BE-t-2x391GB5-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 4050 mm
F 2230 mm
G 4650 mm
E1 1250 mm
E2 1200 mm
H 4300 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 4050 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.