BE-2x580BB1-B01C C
575.87 kW
Defrost: None
Product code: BE-t-2x480GC5-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 155,253 m³/h |
|---|---|
| External surface | 1,354.7 m² |
| Inner volume | 234.9 dm³ |
| Fin material | Aluminium |
| Net weight | 2,044 kg |
| Quantity | 8 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 14,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 89.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-t-2x480GC5-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 338.27 | not rated | not rated | not rated | not rated | not rated |
| 40 | 575.84 | 339.33 | not rated | not rated | not rated | not rated |
| 45 | 806.38 | 574.86 | 340.22 | not rated | not rated | not rated |
| 50 | 1034.56 | 803.69 | 574.10 | 341.14 | not rated | not rated |
| 55 | 1261.66 | 1030.29 | 801.51 | 573.68 | 342.17 | not rated |
| 60 | 1488.13 | 1255.82 | 1026.73 | 799.98 | 573.83 | 343.51 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 263.44 | not rated | not rated | not rated | not rated | not rated |
| 40 | 443.61 | 264.14 | not rated | not rated | not rated | not rated |
| 45 | 617.74 | 442.59 | 264.74 | not rated | not rated | not rated |
| 50 | 789.87 | 615.31 | 441.77 | 265.29 | not rated | not rated |
| 55 | 961.05 | 786.12 | 613.32 | 441.30 | 266.08 | not rated |
| 60 | 1131.72 | 956.05 | 783.04 | 611.94 | 441.32 | 267.11 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 575.840 | 99.87 | 42.5 |
| Low speed (Y) | 443.611 | 76.94 | 26.7 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 4850 mm |
| F | 2230 mm |
| G | 5450 mm |
| E1 | 1150 mm |
| E2 | 2200 mm |
| H | 5100 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5450 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.