BE-t-2x591GB5-C04C C
745.14 kW
Defrost: None
Product code: BE-t-2x491GB1-B04T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 218,372 m³/h |
|---|---|
| External surface | 1,550.2 m² |
| Inner volume | 243.1 dm³ |
| Fin material | Aluminium |
| Net weight | 2,315 kg |
| Quantity | 8 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 22,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 66.0 dB(A) |
|---|---|
| Sound power | 99.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-t-2x491GB1-B04T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 434.47 | not rated | not rated | not rated | not rated | not rated |
| 40 | 744.11 | 435.51 | not rated | not rated | not rated | not rated |
| 45 | 1045.86 | 742.69 | 436.34 | not rated | not rated | not rated |
| 50 | 1344.94 | 1042.25 | 741.47 | 437.18 | not rated | not rated |
| 55 | 1642.82 | 1339.23 | 1039.22 | 740.67 | 438.16 | not rated |
| 60 | 1940.08 | 1635.13 | 1334.39 | 1036.78 | 740.43 | 439.46 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 348.16 | not rated | not rated | not rated | not rated | not rated |
| 40 | 590.38 | 348.92 | not rated | not rated | not rated | not rated |
| 45 | 825.85 | 589.19 | 349.59 | not rated | not rated | not rated |
| 50 | 1059.00 | 822.90 | 588.21 | 350.31 | not rated | not rated |
| 55 | 1291.09 | 1054.40 | 820.44 | 587.59 | 351.10 | not rated |
| 60 | 1522.58 | 1284.89 | 1050.59 | 818.71 | 587.45 | 352.21 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 744.108 | 129.15 | 87.5 |
| Low speed (Y) | 590.383 | 102.38 | 57.9 |
| A | 2910 mm |
|---|---|
| B | 2400 mm |
| C | 5250 mm |
| F | 2330 mm |
| G | 5850 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| H | 5500 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5850 mm |
|---|---|
| Width | 2400 mm |
| Height | 2910 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.