BE-2X780AC5-B01T C
1010.12 kW
Defrost: None
Product code: BE-t-2x680GC1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 239,549 m³/h |
|---|---|
| External surface | 2,842.1 m² |
| Inner volume | 416.5 dm³ |
| Fin material | Aluminium |
| Net weight | 3,532 kg |
| Quantity | 12 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 21,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-t-2x680GC1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 616.58 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1012.38 | 615.58 | not rated | not rated | not rated | not rated |
| 45 | 1396.37 | 1007.68 | 614.79 | not rated | not rated | not rated |
| 50 | 1776.41 | 1388.33 | 1003.75 | 614.32 | not rated | not rated |
| 55 | 2154.62 | 1765.17 | 1381.53 | 1000.78 | 614.43 | not rated |
| 60 | 2531.83 | 2140.25 | 1755.66 | 1376.32 | 999.12 | 615.19 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 471.67 | not rated | not rated | not rated | not rated | not rated |
| 40 | 765.26 | 470.66 | not rated | not rated | not rated | not rated |
| 45 | 1049.42 | 761.28 | 469.81 | not rated | not rated | not rated |
| 50 | 1330.52 | 1042.85 | 757.96 | 469.33 | not rated | not rated |
| 55 | 1610.23 | 1321.50 | 1037.35 | 755.49 | 469.33 | not rated |
| 60 | 1889.16 | 1598.80 | 1313.92 | 1033.18 | 754.14 | 470.05 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 1012.383 | 175.56 | 117.7 |
| Low speed (Y) | 765.255 | 132.73 | 71.8 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 7050 mm |
| F | 2330 mm |
| G | 7650 mm |
| E1 | 1150 mm |
| E2 | 1100 mm |
| E3 | 2200 mm |
| H | 7300 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 7650 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.