BE-291CC5-B04 C
231.68 kW
Defrost: None
Product code: BE-t-380GB1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 63,019 m³/h |
|---|---|
| External surface | 581.7 m² |
| Inner volume | 81.8 dm³ |
| Fin material | Aluminium |
| Net weight | 771 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-t-380GB1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 137.11 | not rated | not rated | not rated | not rated | not rated |
| 40 | 232.28 | 137.27 | not rated | not rated | not rated | not rated |
| 45 | 324.77 | 231.56 | 137.39 | not rated | not rated | not rated |
| 50 | 416.40 | 323.32 | 230.96 | 137.54 | not rated | not rated |
| 55 | 507.63 | 414.24 | 322.08 | 230.52 | 137.74 | not rated |
| 60 | 598.63 | 504.76 | 412.38 | 321.11 | 230.29 | 138.06 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 108.15 | not rated | not rated | not rated | not rated | not rated |
| 40 | 181.34 | 108.21 | not rated | not rated | not rated | not rated |
| 45 | 252.29 | 180.66 | 108.24 | not rated | not rated | not rated |
| 50 | 322.48 | 250.97 | 180.08 | 108.27 | not rated | not rated |
| 55 | 392.32 | 320.56 | 249.84 | 179.64 | 108.40 | not rated |
| 60 | 461.97 | 389.81 | 318.91 | 248.96 | 179.39 | 108.63 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 232.279 | 40.32 | 67.0 |
| Low speed (Y) | 181.341 | 31.45 | 43.1 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 3760 mm |
| F | 1050 mm |
| G | 4360 mm |
| E1 | 1130 mm |
| E2 | 1100 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 4360 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.