BE-2x291DB5-B04T C
328.34 kW
Defrost: None
Product code: BE-t-480GC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 82,463 m³/h |
|---|---|
| External surface | 876.1 m² |
| Inner volume | 125.7 dm³ |
| Fin material | Aluminium |
| Net weight | 1,058 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-t-480GC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 198.32 | not rated | not rated | not rated | not rated | not rated |
| 40 | 328.68 | 198.08 | not rated | not rated | not rated | not rated |
| 45 | 455.44 | 327.25 | 197.81 | not rated | not rated | not rated |
| 50 | 580.99 | 452.94 | 326.02 | 197.68 | not rated | not rated |
| 55 | 705.99 | 577.46 | 450.79 | 325.07 | 197.70 | not rated |
| 60 | 830.67 | 701.45 | 574.43 | 449.11 | 324.50 | 197.96 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 154.03 | not rated | not rated | not rated | not rated | not rated |
| 40 | 252.60 | 153.78 | not rated | not rated | not rated | not rated |
| 45 | 348.19 | 251.40 | 153.58 | not rated | not rated | not rated |
| 50 | 442.80 | 346.16 | 250.40 | 153.45 | not rated | not rated |
| 55 | 536.96 | 439.96 | 344.43 | 249.63 | 153.47 | not rated |
| 60 | 630.88 | 533.34 | 437.56 | 343.10 | 249.20 | 153.68 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 328.676 | 57.01 | 99.8 |
| Low speed (Y) | 252.600 | 43.80 | 62.5 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 4860 mm |
| F | 1050 mm |
| G | 5460 mm |
| E1 | 1130 mm |
| E2 | 1100 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 5460 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.