Skip to Content

Dry cooler BE-t-591GC1-B04 C

Dry cooler BE-t-591GC1-B04 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-591GC1-B04 C

Heat rejection i
549.10 kW
Air flow
134,248 m³/h
Fans
5 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 134,248 m³/h
External surface 1,410.1 m²
Inner volume 194.7 dm³
Fin materialAluminium
Net weight 1,417 kg
Fans
Quantity 5
Diameter 910 mm
Speed 840 rpm
Power 14,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 65.0 dB(A)
Sound power 97.1 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-t-591GC1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
549.104 kW Fluid flow 95.23 m³/h Pressure drop 102.5 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
421.829 kW Fluid flow 73.17 m³/h Pressure drop 64.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 331.37 not rated not rated not rated not rated not rated
40 549.10 331.09 not rated not rated not rated not rated
45 760.39 546.77 330.83 not rated not rated not rated
50 969.51 756.22 544.77 330.70 not rated not rated
55 1177.63 963.58 752.66 543.28 330.84 not rated
60 1385.19 1169.98 958.53 749.90 542.36 331.32

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 257.52 not rated not rated not rated not rated not rated
40 421.83 257.23 not rated not rated not rated not rated
45 580.85 419.94 257.00 not rated not rated not rated
50 738.13 577.56 418.37 256.91 not rated not rated
55 894.61 733.52 574.81 417.23 257.07 not rated
60 1050.64 888.70 729.65 572.75 416.66 257.60

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 549.104 95.23 102.5
Low speed (Y) 421.829 73.17 64.3

Dimensions

Dimension drawing of BE-t-591GC1-B04 C
Dimension drawing
Dimensions as drawn
A 1958 mm
B 1300 mm
C 6460 mm
F 1150 mm
G 7060 mm
E1 1230 mm
E2 1200 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 7060 mm
Width 1300 mm
Height 1958 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.