Skip to Content

Dry cooler BE-t-680GC5-B01 C

Dry cooler BE-t-680GC5-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-680GC5-B01 C

Heat rejection i
492.92 kW
Air flow
123,695 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 123,695 m³/h
External surface 1,314.1 m²
Inner volume 184.6 dm³
Fin materialAluminium
Net weight 1,552 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 88.0 dB(A)
Energy class D
Connections
Inlet 3"
Outlet 3"
Defrost
BE-t-680GC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
492.923 kW Fluid flow 85.49 m³/h Pressure drop 99.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
378.837 kW Fluid flow 65.69 m³/h Pressure drop 62.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 297.38 not rated not rated not rated not rated not rated
40 492.92 297.03 not rated not rated not rated not rated
45 683.07 490.78 296.62 not rated not rated not rated
50 871.40 679.32 488.94 296.43 not rated not rated
55 1058.90 866.11 676.11 487.53 296.47 not rated
60 1245.92 1052.09 861.57 673.58 486.67 296.86

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 230.97 not rated not rated not rated not rated not rated
40 378.84 230.60 not rated not rated not rated not rated
45 522.23 377.04 230.30 not rated not rated not rated
50 664.15 519.18 375.54 230.11 not rated not rated
55 805.39 659.89 516.59 374.40 230.14 not rated
60 946.26 799.96 656.28 514.60 373.75 230.47

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 492.923 85.49 99.3
Low speed (Y) 378.837 65.69 62.1

Dimensions

Dimension drawing of BE-t-680GC5-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 7060 mm
F 1050 mm
G 7660 mm
E1 1130 mm
E2 1100 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 7660 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.