OA/OB-2X263AD1-A01 C
92.82 kW
Defrost: None
Product code: OA/OB-2X263AD5-A01 C
Nominal conditions: oil 80 → 60 °C, air inlet 32 °C, relative humidity 50 %
| Air flow | 33,042 m³/h |
|---|---|
| External surface | 389.0 m² |
| Inner volume | 58.7 dm³ |
| Fin material | Aluminium |
| Net weight | 424 kg |
| Quantity | 4 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 2,400 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | Ø66,7 |
|---|---|
| Outlet | Ø66,7 |
| OA/OB-2X263AD5-A01 C | None |
|---|
Fluid inlet 60–90 °C (outlet = inlet − 20 K, at least 5 K above the air inlet); air inlet 25…50 °C.
B100 80 → 60 °C, air inlet 32 °C
B100; rows: fluid inlet [°C], outlet = inlet − 20 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 60 | 50.11 | 35.60 | 21.73 | not rated | not rated | not rated |
| 70 | 81.07 | 65.17 | 49.98 | 35.50 | 21.66 | not rated |
| 80 | 114.67 | 97.51 | 80.96 | 65.10 | 49.93 | 35.46 |
| 90 | 150.66 | 132.36 | 114.60 | 97.47 | 80.94 | 65.10 |
Nominal conditions: oil 80 → 60 °C, air inlet 32 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 90.816 | 9.53 | 30.3 |
| A | 2240 mm |
|---|---|
| B | 1860 mm |
| C | 2230 mm |
| E1 | 2280 mm |
| E | 1830 mm |
| D | 310 mm |
| D1 | 370 mm |
| D2 | 435 mm |
| D3 | 1035 mm |
| D IN | Ø66,7 |
| D OUT | Ø66,7 |
| Length | 2240 mm |
|---|---|
| Width | 2280 mm |
| Height | 1035 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.