Skip to Content

Oil cooler OA/OB-2X263AD5-A01 C

Oil cooler OA/OB-2X263AD5-A01 C
Illustrative photo

Producer: Karyer · Line: OA/OB (Oil Coolers)

Product code: OA/OB-2X263AD5-A01 C

Heat rejection i
90.82 kW
Air flow
33,042 m³/h
Fans
4 × ⌀630 mm

Nominal conditions: oil 80 → 60 °C, air inlet 32 °C, relative humidity 50 %

Data

Coil
Air flow 33,042 m³/h
External surface 389.0 m²
Inner volume 58.7 dm³
Fin materialAluminium
Net weight 424 kg
Fans
Quantity 4
Diameter 630 mm
Speed 860 rpm
Power 2,400 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 48.0 dB(A)
Sound power 80.0 dB(A)
Energy class D
Connections
Inlet Ø66,7
Outlet Ø66,7
Defrost
OA/OB-2X263AD5-A01 C None

Performance

Outlet 60 °C

Fluid inlet 60–90 °C (outlet = inlet − 20 K, at least 5 K above the air inlet); air inlet 25…50 °C.

B100 80 → 60 °C, air inlet 32 °C

Heat rejection · Single phase
90.816 kW Fluid flow 9.53 m³/h Pressure drop 30.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 20 K)

B100; rows: fluid inlet [°C], outlet = inlet − 20 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Single phase

Heat rejection [kW]: Air inlet × fluid inlet (range 20 K)
Fluid inlet [°C] \ air [°C] 253035404550
60 50.11 35.60 21.73 not rated not rated not rated
70 81.07 65.17 49.98 35.50 21.66 not rated
80 114.67 97.51 80.96 65.10 49.93 35.46
90 150.66 132.36 114.60 97.47 80.94 65.10

Nominal rating

Nominal conditions: oil 80 → 60 °C, air inlet 32 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
Single phase 90.816 9.53 30.3

Dimensions

Dimension drawing of OA/OB-2X263AD5-A01 C
Dimension drawing
Dimensions as drawn
A 2240 mm
B 1860 mm
C 2230 mm
E1 2280 mm
E 1830 mm
D 310 mm
D1 370 mm
D2 435 mm
D3 1035 mm
D IN Ø66,7
D OUT Ø66,7
Overall [mm]
Length 2240 mm
Width 2280 mm
Height 1035 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.