Skip to Content

Oil cooler OA/OB-2X363AD5-A01 C

Oil cooler OA/OB-2X363AD5-A01 C
Illustrative photo

Producer: Karyer · Line: OA/OB (Oil Coolers)

Product code: OA/OB-2X363AD5-A01 C

Heat rejection i
123.20 kW
Air flow
49,563 m³/h
Fans
6 × ⌀630 mm

Nominal conditions: oil 80 → 60 °C, air inlet 32 °C, relative humidity 50 %

Data

Coil
Air flow 49,563 m³/h
External surface 583.6 m²
Inner volume 80.7 dm³
Fin materialAluminium
Net weight 589 kg
Fans
Quantity 6
Diameter 630 mm
Speed 860 rpm
Power 3,600 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 50.0 dB(A)
Sound power 82.0 dB(A)
Energy class D
Connections
Inlet Ø66,7
Outlet Ø66,7
Defrost
OA/OB-2X363AD5-A01 C None

Performance

Outlet 60 °C

Fluid inlet 60–90 °C (outlet = inlet − 20 K, at least 5 K above the air inlet); air inlet 25…50 °C.

B100 80 → 60 °C, air inlet 32 °C

Heat rejection · Single phase
123.201 kW Fluid flow 12.93 m³/h Pressure drop 49.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 20 K)

B100; rows: fluid inlet [°C], outlet = inlet − 20 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Single phase

Heat rejection [kW]: Air inlet × fluid inlet (range 20 K)
Fluid inlet [°C] \ air [°C] 253035404550
60 67.66 47.96 29.23 not rated not rated not rated
70 109.85 88.16 67.48 47.82 29.13 not rated
80 155.91 132.37 109.72 88.05 67.39 47.75
90 205.43 180.21 155.82 132.30 109.67 88.02

Nominal rating

Nominal conditions: oil 80 → 60 °C, air inlet 32 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
Single phase 123.201 12.93 49.8

Dimensions

Dimension drawing of OA/OB-2X363AD5-A01 C
Dimension drawing
Dimensions as drawn
A 3140 mm
B 2760 mm
C 2230 mm
E1 2280 mm
E 2730 mm
D 310 mm
D1 370 mm
D2 435 mm
D3 1035 mm
D IN Ø66,7
D OUT Ø66,7
Overall [mm]
Length 3140 mm
Width 2280 mm
Height 1035 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.