Skip to Content

Compressor rack BSCR-3P-S15-56Y-F-B

Compressor rack BSCR-3P-S15-56Y-F-B
Illustrative photo

Producer: Albassem BRI · Line: Sphinx CompactRack MT

Product code: BSCR-3P-S15-56Y-F-B

Refrigerating capacity i
85.32 kW
Absorbed power
39.38 kW
COP
2.17
Compressors
3 × semi-hermetic reciprocating compressors
Receiver
120 l

Nominal conditions: evaporating -10 °C, condensing 45 °C (dew points), superheat 10 K, subcooling 3 K; refrigerant R404A where rated.

Data

Rack
ApplicationMedium temperature (MT)
Compressors3 × semi-hermetic reciprocating compressors
Liquid receiver 120 l
Net weight 610 kg
Electrical
Max. current 92.1 A
Starting current 136.2 A
Connections
Suction 2"5/8
Liquid 1"3/8
Discharge 1"5/8
Liquid set
L / W / H 714/455/1834 mm
Weight 120 kg

Performance

Evaporating temperature -50…5 °C, condensing temperature 20…55 °C (dew points); superheat 10 K, subcooling 3 K.

R404A, evaporating -10 °C, condensing 45 °C (dew points; superheat 10 K, subcooling 3 K)

Refrigerating capacity
85.32 kW
Absorbed power
39.38 kW
COP
2.17
Current
73.8 A
Heat rejection
124.70 kW

Heat rejection = refrigerating capacity + absorbed power. COP = refrigerating capacity / absorbed power.

Standard points

Te [°C] Tc [°C] Refrigerating capacity [kW] Absorbed power [kW] COP Current [A]
-10 40 93.71 37.28 2.51 71.6
-10 45 85.32 39.38 2.17 73.8

Evaporating × condensing temperature (dew points)

R404A; rows: condensing temperature Tc [°C]; columns: evaporating temperature Te [°C]. The highlighted cell is the nominal point. "—": outside the compressors' operating envelope.

Capacity [kW]

Capacity [kW]: Evaporating × condensing temperature (dew points)
Tc \ Te [°C] -40-35-30-25-20-15-10-5
20 30.79 40.75 52.57 66.68 83.54 103.58 127.26 155.00
25 27.85 37.33 48.49 61.76 77.60 96.46 118.79 145.05
30 24.94 33.94 44.45 56.89 71.73 89.41 110.41 135.18
35 22.02 30.54 40.40 52.02 65.87 82.39 102.06 125.36
40 19.06 27.10 36.31 47.13 59.98 75.35 93.71 115.55
45 16.03 23.58 32.15 42.16 54.04 68.26 85.32 105.72
50 12.91 19.97 27.90 37.10 48.01 61.10 76.87 95.85
55 not rated not rated 23.53 31.92 41.87 53.85 68.35 85.93

Power [kW]

Power [kW]: Evaporating × condensing temperature (dew points)
Tc \ Te [°C] -40-35-30-25-20-15-10-5
20 15.85 18.15 20.48 22.73 24.77 26.46 27.68 28.30
25 16.15 18.69 21.32 23.91 26.34 28.47 30.19 31.36
30 16.46 19.22 22.13 25.06 27.87 30.45 32.65 34.37
35 16.71 19.70 22.89 26.14 29.33 32.34 35.03 37.28
40 16.89 20.10 23.55 27.13 30.69 34.12 37.28 40.06
45 16.96 20.38 24.09 27.97 31.90 35.75 39.38 42.68
50 16.88 20.49 24.46 28.65 32.94 37.19 41.28 45.09
55 not rated not rated 24.63 29.12 33.76 38.41 42.96 47.27

COP

COP: Evaporating × condensing temperature (dew points)
Tc \ Te [°C] -40-35-30-25-20-15-10-5
20 1.94 2.25 2.57 2.93 3.37 3.92 4.60 5.48
25 1.72 2.00 2.27 2.58 2.95 3.39 3.93 4.62
30 1.52 1.77 2.01 2.27 2.57 2.94 3.38 3.93
35 1.32 1.55 1.76 1.99 2.25 2.55 2.91 3.36
40 1.13 1.35 1.54 1.74 1.95 2.21 2.51 2.88
45 0.95 1.16 1.33 1.51 1.69 1.91 2.17 2.48
50 0.77 0.97 1.14 1.29 1.46 1.64 1.86 2.13
55 not rated not rated 0.96 1.10 1.24 1.40 1.59 1.82

Dimensions

Dimension drawing of BSCR-3P-S15-56Y-F-B
Dimension drawing
Dimensions as drawn
L 1790 mm
P 825 mm
H 1255 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.