Product code: BKMR-2N-V15-71Y-F-B

Refrigerating capacity i
22.33 kW
Absorbed power
16.97 kW
COP
1.32
Compressors
2 × semi-hermetic reciprocating compressors
Receiver
60 l

Nominal conditions: evaporating -35 °C, condensing 40 °C (dew points), superheat 10 K, subcooling 3 K; refrigerant R404A where rated.

Data

Rack
ApplicationLow temperature (LT)
Compressors2 × semi-hermetic reciprocating compressors
Liquid receiver 60 l
Net weight 575 kg
Electrical
Max. current 64.4 A
Starting current 107.0 A
Connections
Suction 2"5/8
Liquid 7/8"
Discharge 1"3/8
Liquid set
L / W / H 666/402/1366 mm
Weight 90 kg

Performance

Evaporating temperature -50…5 °C, condensing temperature 20…55 °C (dew points); superheat 10 K, subcooling 3 K.

R404A, evaporating -35 °C, condensing 40 °C (dew points; superheat 10 K, subcooling 3 K)

Refrigerating capacity
22.33 kW
Absorbed power
16.97 kW
COP
1.32
Current
35.6 A
Heat rejection
39.30 kW

Heat rejection = refrigerating capacity + absorbed power. COP = refrigerating capacity / absorbed power.

Standard points

Te [°C] Tc [°C] Refrigerating capacity [kW] Absorbed power [kW] COP Current [A]
-35 40 22.33 16.97 1.32 35.6
-35 45 19.43 17.13 1.13 35.8

Evaporating × condensing temperature (dew points)

R404A; rows: condensing temperature Tc [°C]; columns: evaporating temperature Te [°C]. The highlighted cell is the nominal point. "—": outside the compressors' operating envelope.

Capacity [kW]

Capacity [kW]: Evaporating × condensing temperature (dew points)
Tc \ Te [°C] -45-40-35-30-25-20-15-10-5
20 18.29 25.44 33.68 43.37 54.90 68.65 85.01 104.38 127.12
25 16.17 23.06 30.89 40.02 50.83 63.72 79.08 97.30 118.77
30 14.02 20.64 28.06 36.65 46.76 58.81 73.17 90.26 110.48
35 11.82 18.18 25.21 33.26 42.69 53.90 67.29 83.27 102.25
40 9.60 15.70 22.33 29.85 38.61 49.00 61.43 76.31 94.07
45 7.36 13.18 19.43 26.42 34.52 44.11 55.60 69.39 85.95
50 not rated 10.66 16.51 22.98 30.44 39.24 49.79 62.53 not rated
55 not rated not rated not rated 19.54 26.36 34.38 44.03 55.73 not rated

Power [kW]

Power [kW]: Evaporating × condensing temperature (dew points)
Tc \ Te [°C] -45-40-35-30-25-20-15-10-5
20 11.46 13.29 15.29 17.34 19.32 21.11 22.58 23.63 24.12
25 11.51 13.54 15.78 18.12 20.42 22.57 24.45 25.94 26.92
30 11.54 13.77 16.25 18.86 21.49 24.00 26.28 28.21 29.66
35 11.53 13.95 16.66 19.54 22.48 25.34 28.02 30.39 32.32
40 11.42 14.03 16.97 20.12 23.36 26.58 29.64 32.44 34.85
45 11.18 13.97 17.13 20.54 24.09 27.65 31.11 34.33 37.21
50 not rated 13.73 17.11 20.78 24.63 28.53 32.37 36.01 not rated
55 not rated not rated not rated 20.80 24.94 29.18 33.39 37.46 not rated

COP

COP: Evaporating × condensing temperature (dew points)
Tc \ Te [°C] -45-40-35-30-25-20-15-10-5
20 1.60 1.91 2.20 2.50 2.84 3.25 3.76 4.42 5.27
25 1.41 1.70 1.96 2.21 2.49 2.82 3.23 3.75 4.41
30 1.21 1.50 1.73 1.94 2.18 2.45 2.78 3.20 3.72
35 1.03 1.30 1.51 1.70 1.90 2.13 2.40 2.74 3.16
40 0.84 1.12 1.32 1.48 1.65 1.84 2.07 2.35 2.70
45 0.66 0.94 1.13 1.29 1.43 1.60 1.79 2.02 2.31
50 not rated 0.78 0.96 1.11 1.24 1.38 1.54 1.74 not rated
55 not rated not rated not rated 0.94 1.06 1.18 1.32 1.49 not rated

Dimensions

Dimension drawing of BKMR-2N-V15-71Y-F-B
Dimension drawing
Dimensions as drawn
L 1915 mm
P 800 mm
H 1500 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.