Compressor rack BKMR-2P-V25-93Y-F-B

Compressor rack BKMR-2P-V25-93Y-F-B
Illustrative photo

Producer: Albassem BRI · Line: Khufu ModularRack MT

Product code: BKMR-2P-V25-93Y-F-B

Refrigerating capacity i
87.76 kW
Absorbed power
41.95 kW
COP
2.09
Compressors
2 × semi-hermetic reciprocating compressors
Receiver
120 l

Nominal conditions: evaporating -10 °C, condensing 45 °C (dew points), superheat 10 K, subcooling 3 K; refrigerant R404A where rated.

Data

Rack
ApplicationMedium temperature (MT)
Compressors2 × semi-hermetic reciprocating compressors
Liquid receiver 120 l
Net weight 555 kg
Electrical
Max. current 104.6 A
Starting current 170.6 A
Connections
Suction 3"1/8
Liquid 1"3/8
Discharge 1"5/8
Liquid set
L / W / H 714/455/1834 mm
Weight 130 kg

Performance

Evaporating temperature -50…5 °C, condensing temperature 20…55 °C (dew points); superheat 10 K, subcooling 3 K.

R404A, evaporating -10 °C, condensing 45 °C (dew points; superheat 10 K, subcooling 3 K)

Refrigerating capacity
87.76 kW
Absorbed power
41.95 kW
COP
2.09
Current
74.2 A
Heat rejection
129.71 kW

Heat rejection = refrigerating capacity + absorbed power. COP = refrigerating capacity / absorbed power.

Standard points

Te [°C] Tc [°C] Refrigerating capacity [kW] Absorbed power [kW] COP Current [A]
-10 40 97.93 40.50 2.42 72.5
-10 45 87.76 41.95 2.09 74.2

Evaporating × condensing temperature (dew points)

R404A; rows: condensing temperature Tc [°C]; columns: evaporating temperature Te [°C]. The highlighted cell is the nominal point. "—": outside the compressors' operating envelope.

Capacity [kW]

Capacity [kW]: Evaporating × condensing temperature (dew points)
Tc \ Te [°C] -40-35-30-25-20-15-10-5
20 30.68 41.97 55.72 72.20 91.70 114.50 140.86 171.02
25 26.94 37.44 50.21 65.55 83.74 105.07 129.81 158.23
30 23.38 33.08 44.89 59.09 75.98 95.84 118.97 145.65
35 19.99 28.91 39.76 52.83 68.41 86.82 108.34 133.28
40 16.80 24.93 34.82 46.77 61.06 78.01 97.93 121.13
45 13.79 21.15 30.09 40.92 53.93 69.44 87.76 109.24
50 11.00 17.58 25.58 35.30 47.03 61.11 77.85 97.61
55 not rated not rated 21.30 29.92 40.40 53.05 68.23 86.31

Power [kW]

Power [kW]: Evaporating × condensing temperature (dew points)
Tc \ Te [°C] -40-35-30-25-20-15-10-5
20 17.14 20.04 22.89 25.60 28.12 30.40 32.36 33.95
25 17.16 20.36 23.54 26.63 29.58 32.31 34.77 36.91
30 17.03 20.51 24.01 27.46 30.80 33.98 36.93 39.59
35 16.76 20.50 24.30 28.09 31.82 35.42 38.83 42.00
40 16.37 20.35 24.43 28.54 32.63 36.64 40.50 44.16
45 15.86 20.06 24.40 28.82 33.26 37.66 41.95 46.07
50 15.25 19.65 24.24 28.95 33.71 38.48 43.18 47.76
55 not rated not rated 23.95 28.92 34.00 39.12 44.21 49.23

COP

COP: Evaporating × condensing temperature (dew points)
Tc \ Te [°C] -40-35-30-25-20-15-10-5
20 1.79 2.09 2.43 2.82 3.26 3.77 4.35 5.04
25 1.57 1.84 2.13 2.46 2.83 3.25 3.73 4.29
30 1.37 1.61 1.87 2.15 2.47 2.82 3.22 3.68
35 1.19 1.41 1.64 1.88 2.15 2.45 2.79 3.17
40 1.03 1.22 1.43 1.64 1.87 2.13 2.42 2.74
45 0.87 1.05 1.23 1.42 1.62 1.84 2.09 2.37
50 0.72 0.89 1.06 1.22 1.40 1.59 1.80 2.04
55 not rated not rated 0.89 1.03 1.19 1.36 1.54 1.75

Dimensions

Dimension drawing of BKMR-2P-V25-93Y-F-B
Dimension drawing
Dimensions as drawn
L 1915 mm
P 800 mm
H 1500 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.