BKMR-2P-Z40-126Y-F-B
122.13 kW
Defrost: None
Product code: BKMR-2P-Z40-126Y-F-C
Nominal conditions: evaporating -10 °C, condensing 45 °C (dew points), superheat 10 K, subcooling 3 K; refrigerant R404A where rated.
| Application | Medium temperature (MT) |
|---|---|
| Compressors | 2 × semi-hermetic reciprocating compressors |
| Liquid receiver | 150 l |
| Net weight | 670 kg |
| Max. current | 143.8 A |
|---|---|
| Starting current | 231.1 A |
| Suction | 4"1/8 |
|---|---|
| Liquid | 1"3/8 |
| Discharge | 2"1/8 |
| L / W / H | 790/538/1605 mm |
|---|---|
| Weight | 150 kg |
Evaporating temperature -50…5 °C, condensing temperature 20…55 °C (dew points); superheat 10 K, subcooling 3 K.
R404A, evaporating -10 °C, condensing 45 °C (dew points; superheat 10 K, subcooling 3 K)
Heat rejection = refrigerating capacity + absorbed power. COP = refrigerating capacity / absorbed power.
| Te [°C] | Tc [°C] | Refrigerating capacity [kW] | Absorbed power [kW] | COP | Current [A] |
|---|---|---|---|---|---|
| -10 | 40 | 136.12 | 52.16 | 2.61 | 91.3 |
| -10 | 45 | 122.13 | 54.26 | 2.25 | 94.1 |
R404A; rows: condensing temperature Tc [°C]; columns: evaporating temperature Te [°C]. The highlighted cell is the nominal point. "—": outside the compressors' operating envelope.
| Tc \ Te [°C] | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 5 |
|---|---|---|---|---|---|---|---|---|---|---|
| 20 | 39.53 | 53.74 | 71.74 | 93.97 | 120.89 | 152.95 | 190.60 | 234.22 | 284.17 | not rated |
| 25 | 35.60 | 48.95 | 65.80 | 86.61 | 111.83 | 141.94 | 177.38 | 218.58 | 265.93 | 319.70 |
| 30 | 31.76 | 44.18 | 59.81 | 79.13 | 102.59 | 130.67 | 163.83 | 202.54 | 247.21 | 298.16 |
| 35 | 28.07 | 39.50 | 53.86 | 71.61 | 93.24 | 119.22 | 150.05 | 186.19 | 228.11 | 276.17 |
| 40 | 24.62 | 34.99 | 48.01 | 64.15 | 83.88 | 107.70 | 136.12 | 169.62 | 208.71 | 253.82 |
| 45 | 21.45 | 30.71 | 42.34 | 56.81 | 74.59 | 96.19 | 122.13 | 152.93 | 189.13 | 231.21 |
| 50 | not rated | not rated | 36.94 | 49.68 | 65.46 | 84.78 | 108.19 | 136.23 | 169.47 | 208.48 |
| 55 | not rated | not rated | not rated | not rated | 56.59 | 73.59 | 94.42 | 119.64 | 149.89 | 185.80 |
| Tc \ Te [°C] | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 5 |
|---|---|---|---|---|---|---|---|---|---|---|
| 20 | 24.31 | 27.61 | 30.84 | 33.86 | 36.51 | 38.63 | 40.08 | 40.69 | 40.32 | not rated |
| 25 | 24.38 | 28.00 | 31.67 | 35.22 | 38.51 | 41.37 | 43.66 | 45.22 | 45.91 | 45.55 |
| 30 | 24.37 | 28.28 | 32.32 | 36.36 | 40.23 | 43.78 | 46.87 | 49.33 | 51.01 | 51.76 |
| 35 | 24.30 | 28.43 | 32.80 | 37.27 | 41.68 | 45.87 | 49.70 | 53.01 | 55.64 | 57.45 |
| 40 | 24.16 | 28.47 | 33.12 | 37.97 | 42.86 | 47.64 | 52.16 | 56.27 | 59.80 | 62.61 |
| 45 | 23.96 | 28.39 | 33.27 | 38.45 | 43.78 | 49.10 | 54.26 | 59.11 | 63.50 | 67.26 |
| 50 | not rated | not rated | 33.26 | 38.72 | 44.43 | 50.24 | 56.00 | 61.54 | 66.72 | 71.39 |
| 55 | not rated | not rated | not rated | not rated | 44.83 | 51.07 | 57.37 | 63.56 | 69.49 | 75.01 |
| Tc \ Te [°C] | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 5 |
|---|---|---|---|---|---|---|---|---|---|---|
| 20 | 1.63 | 1.95 | 2.33 | 2.78 | 3.31 | 3.96 | 4.76 | 5.76 | 7.05 | not rated |
| 25 | 1.46 | 1.75 | 2.08 | 2.46 | 2.90 | 3.43 | 4.06 | 4.83 | 5.79 | 7.02 |
| 30 | 1.30 | 1.56 | 1.85 | 2.18 | 2.55 | 2.98 | 3.50 | 4.11 | 4.85 | 5.76 |
| 35 | 1.16 | 1.39 | 1.64 | 1.92 | 2.24 | 2.60 | 3.02 | 3.51 | 4.10 | 4.81 |
| 40 | 1.02 | 1.23 | 1.45 | 1.69 | 1.96 | 2.26 | 2.61 | 3.01 | 3.49 | 4.05 |
| 45 | 0.90 | 1.08 | 1.27 | 1.48 | 1.70 | 1.96 | 2.25 | 2.59 | 2.98 | 3.44 |
| 50 | not rated | not rated | 1.11 | 1.28 | 1.47 | 1.69 | 1.93 | 2.21 | 2.54 | 2.92 |
| 55 | not rated | not rated | not rated | not rated | 1.26 | 1.44 | 1.65 | 1.88 | 2.16 | 2.48 |
| L | 1915 mm |
|---|---|
| P | 1000 mm |
| H | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.