BKMR-3P-6MU-40X
236.00 kW
Defrost: None
Product code: BKMR-3P-6FE-44Y
Nominal conditions: evaporating -10 °C, condensing 45 °C (dew points), superheat 10 K, subcooling 3 K; refrigerant R404A where rated.
| Application | Medium temperature (MT) |
|---|---|
| Compressors | 3 × semi-hermetic reciprocating compressors |
| Liquid receiver | 250 l |
| Net weight | 1,080 kg |
| Max. current | 222.9 A |
|---|---|
| Starting current | 552.6 A |
| Suction | 4"1/8 |
|---|---|
| Liquid | 2"1/8 |
| Discharge | 2"5/8 |
| L / W / H | 739/638/2010 mm |
|---|---|
| Weight | 250 kg |
Evaporating temperature -50…5 °C, condensing temperature 20…55 °C (dew points); superheat 10 K, subcooling 3 K.
R404A, evaporating -10 °C, condensing 45 °C (dew points; superheat 10 K, subcooling 3 K)
Heat rejection = refrigerating capacity + absorbed power. COP = refrigerating capacity / absorbed power.
| Te [°C] | Tc [°C] | Refrigerating capacity [kW] | Absorbed power [kW] | COP | Current [A] |
|---|---|---|---|---|---|
| -10 | 40 | 254.10 | 103.00 | 2.47 | 182.6 |
| -10 | 45 | 229.80 | 107.90 | 2.13 | 189.4 |
R404A; rows: condensing temperature Tc [°C]; columns: evaporating temperature Te [°C]. The highlighted cell is the nominal point. "—": outside the compressors' operating envelope.
| Tc \ Te [°C] | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 |
|---|---|---|---|---|---|---|---|---|---|
| 20 | 82.70 | 109.80 | 142.70 | 182.00 | 228.70 | 283.60 | 348.00 | 423.10 | 511.00 |
| 25 | 75.20 | 100.60 | 131.20 | 168.10 | 212.00 | 263.90 | 325.00 | 396.60 | 480.30 |
| 30 | 67.30 | 91.00 | 119.70 | 154.10 | 195.30 | 244.20 | 301.80 | 369.40 | 448.50 |
| 35 | 59.20 | 81.30 | 108.00 | 140.10 | 178.60 | 224.20 | 278.10 | 341.50 | 415.60 |
| 40 | 51.20 | 71.50 | 96.20 | 126.00 | 161.70 | 204.00 | 254.10 | 313.10 | 382.10 |
| 45 | 43.30 | 61.80 | 84.50 | 111.80 | 144.60 | 183.60 | 229.80 | 284.10 | 347.90 |
| 50 | 35.80 | 52.40 | 72.70 | 97.50 | 127.30 | 162.90 | 205.10 | 254.80 | 313.10 |
| 55 | 28.60 | 43.10 | 61.00 | 83.00 | 109.70 | 141.80 | 179.90 | 224.80 | not rated |
| Tc \ Te [°C] | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 |
|---|---|---|---|---|---|---|---|---|---|
| 20 | 46.30 | 52.60 | 58.70 | 64.60 | 69.90 | 74.40 | 78.00 | 80.50 | 81.50 |
| 25 | 47.40 | 54.40 | 61.50 | 68.20 | 74.60 | 80.20 | 85.00 | 88.80 | 91.20 |
| 30 | 48.10 | 55.90 | 63.80 | 71.50 | 78.80 | 85.60 | 91.50 | 96.50 | 100.30 |
| 35 | 48.60 | 57.10 | 65.70 | 74.30 | 82.60 | 90.40 | 97.50 | 103.80 | 108.90 |
| 40 | 48.60 | 57.80 | 67.20 | 76.60 | 85.90 | 94.80 | 103.00 | 110.50 | 116.90 |
| 45 | 48.20 | 58.10 | 68.20 | 78.50 | 88.70 | 98.60 | 107.90 | 116.60 | 124.30 |
| 50 | 47.40 | 57.90 | 68.80 | 79.90 | 91.00 | 101.90 | 112.30 | 122.10 | 131.10 |
| 55 | 46.10 | 57.20 | 68.90 | 80.80 | 92.70 | 104.60 | 116.10 | 127.00 | not rated |
| Tc \ Te [°C] | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 |
|---|---|---|---|---|---|---|---|---|---|
| 20 | 1.79 | 2.09 | 2.43 | 2.82 | 3.27 | 3.81 | 4.46 | 5.26 | 6.27 |
| 25 | 1.59 | 1.85 | 2.13 | 2.46 | 2.84 | 3.29 | 3.82 | 4.47 | 5.27 |
| 30 | 1.40 | 1.63 | 1.88 | 2.16 | 2.48 | 2.85 | 3.30 | 3.83 | 4.47 |
| 35 | 1.22 | 1.42 | 1.64 | 1.89 | 2.16 | 2.48 | 2.85 | 3.29 | 3.82 |
| 40 | 1.05 | 1.24 | 1.43 | 1.64 | 1.88 | 2.15 | 2.47 | 2.83 | 3.27 |
| 45 | 0.90 | 1.06 | 1.24 | 1.42 | 1.63 | 1.86 | 2.13 | 2.44 | 2.80 |
| 50 | 0.76 | 0.91 | 1.06 | 1.22 | 1.40 | 1.60 | 1.83 | 2.09 | 2.39 |
| 55 | 0.62 | 0.75 | 0.89 | 1.03 | 1.18 | 1.36 | 1.55 | 1.77 | not rated |
| Length | 2515 mm |
|---|---|
| Width | 1000 mm |
| Height | 1580 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.