BKMR-4P-V35-112Y-F-B
201.57 kW
Defrost: None
Product code: BKMR-5P-V20-84Y-F-C
Nominal conditions: evaporating -10 °C, condensing 45 °C (dew points), superheat 10 K, subcooling 3 K; refrigerant R404A where rated.
| Application | Medium temperature (MT) |
|---|---|
| Compressors | 5 × semi-hermetic reciprocating compressors |
| Liquid receiver | 250 l |
| Net weight | 1,320 kg |
| Max. current | 213.0 A |
|---|---|
| Starting current | 277.0 A |
| Suction | 4"1/8 |
|---|---|
| Liquid | 1"3/8 |
| Discharge | 2"5/8 |
| L / W / H | 739/638/2010 mm |
|---|---|
| Weight | 250 kg |
Evaporating temperature -50…5 °C, condensing temperature 20…55 °C (dew points); superheat 10 K, subcooling 3 K.
R404A, evaporating -10 °C, condensing 45 °C (dew points; superheat 10 K, subcooling 3 K)
Heat rejection = refrigerating capacity + absorbed power. COP = refrigerating capacity / absorbed power.
| Te [°C] | Tc [°C] | Refrigerating capacity [kW] | Absorbed power [kW] | COP | Current [A] |
|---|---|---|---|---|---|
| -10 | 40 | 223.50 | 93.55 | 2.39 | 166.5 |
| -10 | 45 | 199.92 | 97.78 | 2.04 | 172.2 |
R404A; rows: condensing temperature Tc [°C]; columns: evaporating temperature Te [°C]. The highlighted cell is the nominal point. "—": outside the compressors' operating envelope.
| Tc \ Te [°C] | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 |
|---|---|---|---|---|---|---|---|---|
| 20 | 65.85 | 90.43 | 120.69 | 157.20 | 200.57 | 251.37 | 310.17 | 377.46 |
| 25 | 60.49 | 83.60 | 111.96 | 146.18 | 186.86 | 234.60 | 289.98 | 353.54 |
| 30 | 54.92 | 76.40 | 102.73 | 134.52 | 172.36 | 216.89 | 268.70 | 328.37 |
| 35 | 49.26 | 68.99 | 93.15 | 122.36 | 157.23 | 198.39 | 246.48 | 302.11 |
| 40 | 43.66 | 61.50 | 83.37 | 109.86 | 141.62 | 179.28 | 223.50 | 274.93 |
| 45 | 38.25 | 54.09 | 73.54 | 97.19 | 125.70 | 159.72 | 199.93 | 247.00 |
| 50 | 33.15 | 46.88 | 63.80 | 84.52 | 109.66 | 139.90 | 175.95 | 218.53 |
| 55 | not rated | not rated | 54.33 | 72.00 | 93.67 | 120.02 | 151.79 | 189.75 |
| Tc \ Te [°C] | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 |
|---|---|---|---|---|---|---|---|---|
| 20 | 39.22 | 45.16 | 50.89 | 56.26 | 61.11 | 65.29 | 68.65 | 71.01 |
| 25 | 39.91 | 46.62 | 53.26 | 59.69 | 65.74 | 71.26 | 76.10 | 80.10 |
| 30 | 40.40 | 47.77 | 55.22 | 62.59 | 69.74 | 76.51 | 82.73 | 88.25 |
| 35 | 40.69 | 48.62 | 56.77 | 65.00 | 73.14 | 81.04 | 88.54 | 95.49 |
| 40 | 40.79 | 49.18 | 57.94 | 66.91 | 75.94 | 84.88 | 93.55 | 101.82 |
| 45 | 40.73 | 49.47 | 58.73 | 68.34 | 78.16 | 88.03 | 97.78 | 107.26 |
| 50 | 40.51 | 49.50 | 59.15 | 69.31 | 79.81 | 90.50 | 101.22 | 111.82 |
| 55 | not rated | not rated | 59.23 | 69.82 | 80.90 | 92.32 | 103.91 | 115.52 |
| Tc \ Te [°C] | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 |
|---|---|---|---|---|---|---|---|---|
| 20 | 1.68 | 2.00 | 2.37 | 2.79 | 3.28 | 3.85 | 4.52 | 5.32 |
| 25 | 1.52 | 1.79 | 2.10 | 2.45 | 2.84 | 3.29 | 3.81 | 4.41 |
| 30 | 1.36 | 1.60 | 1.86 | 2.15 | 2.47 | 2.83 | 3.25 | 3.72 |
| 35 | 1.21 | 1.42 | 1.64 | 1.88 | 2.15 | 2.45 | 2.78 | 3.16 |
| 40 | 1.07 | 1.25 | 1.44 | 1.64 | 1.86 | 2.11 | 2.39 | 2.70 |
| 45 | 0.94 | 1.09 | 1.25 | 1.42 | 1.61 | 1.81 | 2.04 | 2.30 |
| 50 | 0.82 | 0.95 | 1.08 | 1.22 | 1.37 | 1.55 | 1.74 | 1.95 |
| 55 | not rated | not rated | 0.92 | 1.03 | 1.16 | 1.30 | 1.46 | 1.64 |
| L | 3715 mm |
|---|---|
| P | 1000 mm |
| H | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.