BKMR-6P-6MU-40X
472.08 kW
Defrost: None
Product code: BKMR-6P-6FE-44Y
Nominal conditions: evaporating -10 °C, condensing 45 °C (dew points), superheat 10 K, subcooling 3 K; refrigerant R404A where rated.
| Application | Medium temperature (MT) |
|---|---|
| Compressors | 6 × semi-hermetic reciprocating compressors |
| Liquid receiver | 350 l |
| Net weight | 2,195 kg |
| Max. current | 445.9 A |
|---|---|
| Starting current | 775.6 A |
| Suction | - |
|---|---|
| Liquid | - |
| Discharge | - |
| L / W / H | 993/856/1942 mm |
|---|---|
| Weight | 290 kg |
Evaporating temperature -50…5 °C, condensing temperature 20…55 °C (dew points); superheat 10 K, subcooling 3 K.
R404A, evaporating -10 °C, condensing 45 °C (dew points; superheat 10 K, subcooling 3 K)
Heat rejection = refrigerating capacity + absorbed power. COP = refrigerating capacity / absorbed power.
Rated from the compressors' data: this rack is no longer in the manufacturer's current program.
| Te [°C] | Tc [°C] | Refrigerating capacity [kW] | Absorbed power [kW] | COP | Current [A] |
|---|---|---|---|---|---|
| -10 | 40 | 508.20 | 206.04 | 2.47 | 365.2 |
| -10 | 45 | 459.60 | 215.88 | 2.13 | 378.8 |
R404A; rows: condensing temperature Tc [°C]; columns: evaporating temperature Te [°C]. The highlighted cell is the nominal point. "—": outside the compressors' operating envelope.
| Tc \ Te [°C] | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 |
|---|---|---|---|---|---|---|---|---|---|
| 20 | 165.48 | 219.72 | 285.36 | 364.08 | 457.44 | 567.24 | 695.88 | 846.24 | 1022.04 |
| 25 | 150.48 | 201.12 | 262.44 | 336.24 | 423.96 | 527.88 | 650.04 | 793.32 | 960.60 |
| 30 | 134.64 | 181.92 | 239.28 | 308.28 | 390.60 | 488.28 | 603.48 | 738.84 | 896.88 |
| 35 | 118.44 | 162.48 | 216.00 | 280.32 | 357.12 | 448.44 | 556.20 | 683.04 | 831.24 |
| 40 | 102.36 | 143.04 | 192.48 | 252.00 | 323.28 | 408.00 | 508.20 | 626.16 | 764.16 |
| 45 | 86.64 | 123.72 | 168.96 | 223.68 | 289.20 | 367.20 | 459.60 | 568.32 | 695.76 |
| 50 | 71.64 | 104.76 | 145.44 | 195.00 | 254.64 | 325.80 | 410.16 | 509.52 | 626.16 |
| 55 | 57.24 | 86.16 | 122.04 | 166.08 | 219.48 | 283.56 | 359.76 | 449.64 | not rated |
| Tc \ Te [°C] | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 |
|---|---|---|---|---|---|---|---|---|---|
| 20 | 92.52 | 105.12 | 117.48 | 129.12 | 139.80 | 148.92 | 156.12 | 160.92 | 163.08 |
| 25 | 94.80 | 108.84 | 122.88 | 136.44 | 149.16 | 160.44 | 170.04 | 177.48 | 182.40 |
| 30 | 96.24 | 111.84 | 127.56 | 142.92 | 157.56 | 171.12 | 183.12 | 193.08 | 200.64 |
| 35 | 97.08 | 114.12 | 131.40 | 148.56 | 165.24 | 180.84 | 195.12 | 207.60 | 217.80 |
| 40 | 97.20 | 115.56 | 134.40 | 153.24 | 171.84 | 189.48 | 206.04 | 220.92 | 233.88 |
| 45 | 96.36 | 116.16 | 136.44 | 157.08 | 177.36 | 197.16 | 215.88 | 233.16 | 248.64 |
| 50 | 94.80 | 115.80 | 137.64 | 159.84 | 181.92 | 203.76 | 224.64 | 244.20 | 262.20 |
| 55 | 92.28 | 114.48 | 137.76 | 161.52 | 185.40 | 209.16 | 232.20 | 254.04 | not rated |
| Tc \ Te [°C] | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 |
|---|---|---|---|---|---|---|---|---|---|
| 20 | 1.79 | 2.09 | 2.43 | 2.82 | 3.27 | 3.81 | 4.46 | 5.26 | 6.27 |
| 25 | 1.59 | 1.85 | 2.14 | 2.46 | 2.84 | 3.29 | 3.82 | 4.47 | 5.27 |
| 30 | 1.40 | 1.63 | 1.88 | 2.16 | 2.48 | 2.85 | 3.30 | 3.83 | 4.47 |
| 35 | 1.22 | 1.42 | 1.64 | 1.89 | 2.16 | 2.48 | 2.85 | 3.29 | 3.82 |
| 40 | 1.05 | 1.24 | 1.43 | 1.64 | 1.88 | 2.15 | 2.47 | 2.83 | 3.27 |
| 45 | 0.90 | 1.07 | 1.24 | 1.42 | 1.63 | 1.86 | 2.13 | 2.44 | 2.80 |
| 50 | 0.76 | 0.90 | 1.06 | 1.22 | 1.40 | 1.60 | 1.83 | 2.09 | 2.39 |
| 55 | 0.62 | 0.75 | 0.89 | 1.03 | 1.18 | 1.36 | 1.55 | 1.77 | not rated |
| Length | 4215 mm |
|---|---|
| Width | 1400 mm |
| Height | 1600 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.