BHSR-5N-ZF33
31.90 kW
Defrost: None
Product code: BHSR-5N-ZF24
Nominal conditions: evaporating -35 °C, condensing 40 °C (dew points), superheat 10 K, subcooling 3 K; refrigerant R404A where rated.
| Application | Low temperature (LT) |
|---|---|
| Compressors | 5 × scroll compressors |
| Liquid receiver | 60 l |
| Net weight | 820 kg |
| Max. current | 62.5 A |
|---|---|
| Starting current | 149.5 A |
| Suction | 2"5/8 |
|---|---|
| Liquid | 1"1/8 |
| Discharge | 1"3/8 |
| L / W / H | 666/402/1366 mm |
|---|---|
| Weight | 90 kg |
Evaporating temperature -50…5 °C, condensing temperature 20…55 °C (dew points); superheat 10 K, subcooling 3 K.
R404A, evaporating -35 °C, condensing 40 °C (dew points; superheat 10 K, subcooling 3 K)
Heat rejection = refrigerating capacity + absorbed power. COP = refrigerating capacity / absorbed power.
| Te [°C] | Tc [°C] | Refrigerating capacity [kW] | Absorbed power [kW] | COP | Current [A] |
|---|---|---|---|---|---|
| -35 | 40 | 23.20 | 22.60 | 1.03 | 51.9 |
| -35 | 45 | 21.10 | 24.40 | 0.86 | 53.8 |
R404A; rows: condensing temperature Tc [°C]; columns: evaporating temperature Te [°C]. The highlighted cell is the nominal point. "—": outside the compressors' operating envelope.
| Tc \ Te [°C] | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 |
|---|---|---|---|---|---|---|---|---|
| 20 | 23.40 | 30.20 | 38.20 | 47.80 | 59.10 | 72.40 | 88.10 | 106.30 |
| 25 | 22.10 | 28.60 | 36.20 | 45.20 | 55.90 | 68.40 | 83.20 | 100.40 |
| 30 | 20.70 | 26.90 | 34.10 | 42.60 | 52.60 | 64.30 | 78.20 | 94.40 |
| 35 | 19.30 | 25.10 | 31.90 | 39.80 | 49.10 | 60.10 | 73.10 | 88.30 |
| 40 | 17.60 | 23.20 | 29.50 | 36.80 | 45.50 | 55.70 | 67.70 | 81.90 |
| 45 | 15.80 | 21.10 | 26.90 | 33.70 | 41.60 | 51.00 | 62.10 | 75.30 |
| 50 | 13.80 | 18.70 | 24.10 | 30.30 | 37.50 | 46.10 | 56.30 | 68.40 |
| 55 | 11.50 | 16.00 | 21.00 | 26.60 | 33.10 | 40.90 | 50.10 | 61.30 |
| Tc \ Te [°C] | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 |
|---|---|---|---|---|---|---|---|---|
| 20 | 15.60 | 16.30 | 17.00 | 17.80 | 18.70 | 19.80 | 21.10 | 22.60 |
| 25 | 17.00 | 17.70 | 18.50 | 19.30 | 20.20 | 21.30 | 22.50 | 23.90 |
| 30 | 18.40 | 19.30 | 20.10 | 21.00 | 21.90 | 22.90 | 24.10 | 25.40 |
| 35 | 19.90 | 20.90 | 21.80 | 22.80 | 23.80 | 24.80 | 25.90 | 27.20 |
| 40 | 21.50 | 22.60 | 23.70 | 24.70 | 25.80 | 26.80 | 27.90 | 29.20 |
| 45 | 23.10 | 24.40 | 25.60 | 26.80 | 27.90 | 29.00 | 30.20 | 31.40 |
| 50 | 24.70 | 26.30 | 27.70 | 29.00 | 30.20 | 31.40 | 32.60 | 33.80 |
| 55 | 26.40 | 28.20 | 29.80 | 31.20 | 32.60 | 33.90 | 35.10 | 36.40 |
| Tc \ Te [°C] | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 |
|---|---|---|---|---|---|---|---|---|
| 20 | 1.50 | 1.85 | 2.25 | 2.69 | 3.16 | 3.66 | 4.18 | 4.70 |
| 25 | 1.30 | 1.62 | 1.96 | 2.34 | 2.77 | 3.21 | 3.70 | 4.20 |
| 30 | 1.12 | 1.39 | 1.70 | 2.03 | 2.40 | 2.81 | 3.24 | 3.72 |
| 35 | 0.97 | 1.20 | 1.46 | 1.75 | 2.06 | 2.42 | 2.82 | 3.25 |
| 40 | 0.82 | 1.03 | 1.24 | 1.49 | 1.76 | 2.08 | 2.43 | 2.80 |
| 45 | 0.68 | 0.86 | 1.05 | 1.26 | 1.49 | 1.76 | 2.06 | 2.40 |
| 50 | 0.56 | 0.71 | 0.87 | 1.04 | 1.24 | 1.47 | 1.73 | 2.02 |
| 55 | 0.44 | 0.57 | 0.70 | 0.85 | 1.02 | 1.21 | 1.43 | 1.68 |
| Length | 3115 mm |
|---|---|
| Width | 800 mm |
| Height | 1500 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.