Compressor rack BHSR-5N-ZF48

Illustrative photo

Producer: Albassem BRI · Line: Hatshepsut ScrollRack LT

Product code: BHSR-5N-ZF48

Refrigerating capacity i
47.60 kW
Absorbed power
48.50 kW
COP
0.98
Compressors
5 × scroll compressors
Receiver
150 l

Nominal conditions: evaporating -35 °C, condensing 40 °C (dew points), superheat 10 K, subcooling 3 K; refrigerant R404A where rated.

Data

Rack
ApplicationLow temperature (LT)
Compressors5 × scroll compressors
Liquid receiver 150 l
Net weight 930 kg
Electrical
Max. current 122.5 A
Starting current 295.5 A
Connections
Suction 3"1/8
Liquid 1"3/8
Discharge 1"3/8
Liquid set
L / W / H 790/538/1605 mm
Weight 150 kg

Performance

Evaporating temperature -50…5 °C, condensing temperature 20…55 °C (dew points); superheat 10 K, subcooling 3 K.

R404A, evaporating -35 °C, condensing 40 °C (dew points; superheat 10 K, subcooling 3 K)

Refrigerating capacity
47.60 kW
Absorbed power
48.50 kW
COP
0.98
Current
93.4 A
Heat rejection
96.10 kW

Heat rejection = refrigerating capacity + absorbed power. COP = refrigerating capacity / absorbed power.

Standard points

Te [°C] Tc [°C] Refrigerating capacity [kW] Absorbed power [kW] COP Current [A]
-35 40 47.60 48.50 0.98 93.4
-35 45 43.10 52.70 0.82 98.4

Evaporating × condensing temperature (dew points)

R404A; rows: condensing temperature Tc [°C]; columns: evaporating temperature Te [°C]. The highlighted cell is the nominal point. "—": outside the compressors' operating envelope.

Capacity [kW]

Capacity [kW]: Evaporating × condensing temperature (dew points)
Tc \ Te [°C] -40-35-30-25-20-15-10-5
20 50.60 64.10 80.70 100.70 124.60 152.60 185.00 222.10
25 47.30 60.20 76.00 95.10 117.70 144.30 175.10 210.50
30 44.00 56.20 71.10 89.10 110.40 135.50 164.60 198.20
35 40.50 52.00 65.90 82.70 102.70 126.20 153.60 185.20
40 36.90 47.60 60.50 76.10 94.70 116.50 142.10 171.80
45 33.30 43.10 55.00 69.20 86.30 106.40 130.10 157.70
50 29.70 38.50 49.20 62.10 77.60 96.00 117.70 143.20
55 26.10 33.90 43.40 54.80 68.60 85.20 104.90 128.20

Power [kW]

Power [kW]: Evaporating × condensing temperature (dew points)
Tc \ Te [°C] -40-35-30-25-20-15-10-5
20 33.10 34.50 36.10 37.90 40.00 42.30 45.00 48.00
25 36.00 37.60 39.30 41.20 43.30 45.60 48.10 51.00
30 39.20 41.00 42.80 44.80 46.90 49.20 51.80 54.50
35 42.60 44.60 46.60 48.80 51.00 53.30 55.90 58.60
40 46.20 48.50 50.80 53.10 55.50 57.90 60.50 63.10
45 50.10 52.70 55.30 57.80 60.40 62.90 65.60 68.30
50 54.20 57.20 60.10 62.90 65.70 68.40 71.20 74.00
55 58.50 62.00 65.20 68.40 71.40 74.40 77.30 80.20

COP

COP: Evaporating × condensing temperature (dew points)
Tc \ Te [°C] -40-35-30-25-20-15-10-5
20 1.53 1.86 2.24 2.66 3.12 3.61 4.11 4.63
25 1.31 1.60 1.93 2.31 2.72 3.16 3.64 4.13
30 1.12 1.37 1.66 1.99 2.35 2.75 3.18 3.64
35 0.95 1.17 1.41 1.69 2.01 2.37 2.75 3.16
40 0.80 0.98 1.19 1.43 1.71 2.01 2.35 2.72
45 0.66 0.82 0.99 1.20 1.43 1.69 1.98 2.31
50 0.55 0.67 0.82 0.99 1.18 1.40 1.65 1.94
55 0.45 0.55 0.67 0.80 0.96 1.15 1.36 1.60

Dimensions

Overall [mm]
Length 3115 mm
Width 800 mm
Height 1500 mm

Downloads