EA-DA-x-150BE7-B21 C
8.88 kW
Defrost: None
Product code: EA-DA-145AE7-C23 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,485 m³/h |
|---|---|
| Air throw | 16 m |
| External surface | 38.0 m² |
| Inner volume | 11.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 76 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,300 rpm |
| Power | 350 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-DA-145AE7-C23 C | None |
|---|---|
| EA-DA-145AE7-C23 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.58 | 3.58 | 3.59 | 3.61 | 3.61 | 3.59 | 3.56 | 3.60 | 3.82 | 4.13 | 4.03 | 4.00 | 3.95 | 3.87 |
| 5 | 4.53 | 4.59 | 4.65 | 4.70 | 4.71 | 4.70 | 4.66 | 4.70 | 4.98 | 5.38 | 5.24 | 5.18 | 5.11 | 5.00 |
| 6 | 5.42 | 5.57 | 5.70 | 5.81 | 5.86 | 5.87 | 5.84 | 5.86 | 6.20 | 6.71 | 6.51 | 6.44 | 6.33 | 6.17 |
| 7 | 6.25 | 6.51 | 6.69 | 6.88 | 6.99 | 7.03 | 7.03 | 7.06 | 7.48 | 8.09 | 7.86 | 7.76 | 7.63 | 7.39 |
| 8 | 6.96 | 7.32 | 7.64 | 7.92 | 8.10 | 8.21 | 8.24 | 8.29 | 8.79 | 9.51 | 9.25 | 9.14 | 8.96 | 8.68 |
| 9 | 7.64 | 8.09 | 8.51 | 8.87 | 9.12 | 9.27 | 9.35 | 9.45 | 10.03 | 10.88 | 10.63 | 10.52 | 10.33 | 9.99 |
| 10 | 8.24 | 8.82 | 9.34 | 9.80 | 10.11 | 10.32 | 10.43 | 10.56 | 11.21 | 12.17 | 11.89 | 11.76 | 11.57 | 11.23 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.892 |
| SC2 | 0 | 8 | 8.291 |
| SC3 | -18 | 7 | 6.933 |
| SC4 | -25 | 6 | 5.699 |
| SC5 | -34 | 6 | 5.459 |
| A | 1217 mm |
|---|---|
| B | 875 mm |
| C | 710 mm |
| F | 710 mm |
| E | 785 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1217 mm |
|---|---|
| Width | 875 mm |
| Height | 710 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.