EA-DA-163BE7-C27 C
14.33 kW
Defrost: None
Product code: EA-DA-435BE7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 8,158 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 50.6 m² |
| Inner volume | 18.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 131 kg |
| Quantity | 4 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 660 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 76.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-DA-435BE7-C21 C | None |
|---|---|
| EA-DA-435BE7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.43 | 5.79 | 6.10 | 6.35 | 6.49 | 6.54 | 6.51 | 6.66 | 7.09 | 7.68 | 7.47 | 7.40 | 7.31 | 7.16 |
| 5 | 6.63 | 7.19 | 7.70 | 8.13 | 8.40 | 8.52 | 8.55 | 8.71 | 9.26 | 10.04 | 9.74 | 9.63 | 9.45 | 9.15 |
| 6 | 7.62 | 8.39 | 9.09 | 9.70 | 10.04 | 10.32 | 10.45 | 10.67 | 11.36 | 12.36 | 12.06 | 11.93 | 11.70 | 11.31 |
| 7 | ≈ 7.84 | ≈ 9.41 | 10.32 | 11.00 | 11.59 | 11.99 | 12.22 | 12.49 | 13.30 | 14.48 | 14.15 | 14.00 | 13.75 | 13.31 |
| 8 | ≈ 4.54 | ≈ 10.34 | 11.31 | 12.30 | 13.07 | 13.61 | 13.95 | 14.29 | 15.23 | 16.59 | 16.25 | 16.07 | 15.78 | 15.26 |
| 9 | ≈ 3.05 | ≈ 9.36 | ≈ 12.32 | 13.51 | 14.47 | 15.18 | 15.63 | 16.08 | 17.14 | 18.69 | 18.34 | 18.14 | 17.83 | 17.24 |
| 10 | ≈ 3.32 | ≈ 6.39 | ≈ 13.24 | 14.65 | 15.81 | 16.69 | 17.28 | 17.83 | 19.03 | 20.78 | 20.43 | 20.23 | 19.88 | 19.22 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 20.432 |
| SC2 | 0 | 8 | 14.293 |
| SC3 | -18 | 7 | 11.257 |
| SC4 | -25 | 6 | 9.087 |
| SC5 | -34 | 6 | 7.786 |
| A | 2457 mm |
|---|---|
| B | 730 mm |
| C | 530 mm |
| F | 560 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 2035 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2457 mm |
|---|---|
| Width | 730 mm |
| Height | 530 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.