EA-DA-x-450BE7-B22 C
35.20 kW
Defrost: None
Product code: EA-DA-x-450BE7-B21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 28,914 m³/h |
|---|---|
| Air throw | 25 m |
| External surface | 236.6 m² |
| Inner volume | 68.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 315 kg |
| Quantity | 4 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,300 rpm |
| Power | 2,720 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 84.9 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-DA-x-450BE7-B21 C | None |
|---|---|
| EA-DA-x-450BE7-B21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | 14.12 | 15.02 | 15.86 | 16.45 | 16.82 | 17.28 | 18.45 | 20.12 | 19.81 | 19.69 | 19.50 | 19.13 |
| 5 | not rated | not rated | not rated | 18.44 | 19.72 | 20.70 | 21.40 | 22.09 | 23.64 | 25.88 | 25.64 | 25.53 | 25.34 | 24.99 |
| 6 | ≈ 6.07 | ≈ 10.85 | 19.29 | 21.37 | 23.11 | 24.49 | 25.53 | 26.46 | 28.35 | 31.12 | 30.91 | 30.79 | 30.59 | 30.18 |
| 7 | 6.90 | not rated | ≈ 20.51 | ≈ 24.04 | 26.27 | 28.10 | 29.51 | 30.74 | 32.99 | 36.31 | 36.18 | 36.07 | 35.86 | 35.40 |
| 8 | 7.70 | ≈ 7.56 | ≈ 12.50 | ≈ 26.47 | 29.20 | 31.50 | 33.34 | 34.90 | 37.52 | 41.40 | 41.40 | 41.32 | 41.12 | 40.65 |
| 9 | 8.49 | 8.34 | ≈ 8.36 | ≈ 28.70 | 31.91 | 34.70 | 36.99 | 38.93 | 41.93 | 46.38 | 46.54 | 46.50 | 46.35 | 45.89 |
| 10 | 9.26 | 9.11 | ≈ 9.11 | ≈ 17.64 | ≈ 34.40 | 37.70 | 40.46 | 42.80 | 46.19 | 51.21 | 51.60 | 51.61 | 51.52 | 51.09 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 51.601 |
| SC2 | 0 | 8 | 34.902 |
| SC3 | -18 | 7 | 24.975 |
| SC4 | -25 | 6 | 19.290 |
| SC5 | -34 | 6 | 6.048 |
| A | 4487 mm |
|---|---|
| B | 950 mm |
| C | 810 mm |
| F | 710 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 4035 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 4487 mm |
|---|---|
| Width | 950 mm |
| Height | 810 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.