EA-DI-191GG10-A04 C
39.09 kW
Defrost: None
Product code: EA-DI-163GI4-A08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 13,675 m³/h |
|---|---|
| External surface | 271.2 m² |
| Inner volume | 54.0 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 310 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 69.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-DI-163GI4-A08 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 17.63 | 17.76 | 17.94 | 18.13 | 18.19 | 18.15 | 18.02 | 18.32 | 19.47 | 21.13 | 20.64 | 20.46 | 20.22 | 19.88 |
| 5 | 21.89 | 22.28 | 22.66 | 23.02 | 23.15 | 23.14 | 22.99 | 23.23 | 24.64 | 26.70 | 25.95 | 25.67 | 25.26 | 24.61 |
| 6 | 25.85 | 26.61 | 27.31 | 27.91 | 28.22 | 28.28 | 28.09 | 28.28 | 29.97 | 32.45 | 31.46 | 31.07 | 30.49 | 29.53 |
| 7 | 29.53 | 30.75 | 31.67 | 32.60 | 33.14 | 33.36 | 33.27 | 33.48 | 35.46 | 38.35 | 37.19 | 36.70 | 35.95 | 34.72 |
| 8 | 32.66 | 34.38 | 35.87 | 37.17 | 38.01 | 38.46 | 38.49 | 38.74 | 41.02 | 44.34 | 43.03 | 42.44 | 41.55 | 40.01 |
| 9 | 35.75 | 37.86 | 39.79 | 41.48 | 42.59 | 43.21 | 43.42 | 43.80 | 46.43 | 50.25 | 48.91 | 48.26 | 47.23 | 45.39 |
| 10 | 38.49 | 41.13 | 43.55 | 45.65 | 47.10 | 47.92 | 48.28 | 48.73 | 51.66 | 55.90 | 54.44 | 53.75 | 52.68 | 50.72 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 14.64 | 14.63 | 14.71 | 14.83 | 14.87 | 14.83 | 14.72 | 14.97 | 15.92 | 17.29 | 16.88 | 16.74 | 16.53 | 16.23 |
| 5 | 18.18 | 18.25 | 18.45 | 18.67 | 18.76 | 18.73 | 18.59 | 18.79 | 19.94 | 21.61 | 21.01 | 20.77 | 20.43 | 19.89 |
| 6 | 21.54 | 21.88 | 22.24 | 22.59 | 22.72 | 22.72 | 22.58 | 22.73 | 24.08 | 26.08 | 25.28 | 24.96 | 24.48 | 23.68 |
| 7 | 24.75 | 25.35 | 25.94 | 26.47 | 26.74 | 26.79 | 26.64 | 26.76 | 28.33 | 30.62 | 29.67 | 29.26 | 28.63 | not rated |
| 8 | 27.76 | 28.69 | 29.56 | 30.22 | 30.65 | 30.81 | 30.69 | 30.83 | 32.62 | 35.23 | 34.13 | 33.65 | 32.91 | not rated |
| 9 | 30.57 | 31.72 | 32.93 | 33.96 | 34.58 | 34.84 | 34.79 | 34.95 | 36.98 | 39.91 | 38.69 | 38.13 | not rated | not rated |
| 10 | 33.15 | 34.69 | 36.20 | 37.54 | 38.39 | 38.84 | 38.89 | 39.08 | 41.35 | 44.63 | 43.29 | 42.66 | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 54.442 | 43.288 |
| SC2 | 0 | 8 | 38.736 | 30.829 |
| SC3 | -18 | 7 | 32.859 | 26.608 |
| SC4 | -25 | 6 | 27.305 | 22.235 |
| SC5 | -34 | 6 | 26.045 | 21.642 |
| A | 1725 mm |
|---|---|
| B | 1200 mm |
| C | 1150 mm |
| F | 1160 mm |
| G | 1740 mm |
| E | 1335 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 1725 mm |
|---|---|
| Width | 1740 mm |
| Height | 1150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.