EA-DI-180GC7-A01 C
22.47 kW
Defrost: None
Product code: EA-DI-191GC10-A04 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 28,889 m³/h |
|---|---|
| External surface | 63.5 m² |
| Inner volume | 26.9 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 272 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 67.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | E |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-DI-191GC10-A04 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.19 | 9.00 | 8.86 | 8.75 | 8.60 | 8.44 | 8.27 | 8.25 | 8.69 | 9.33 | 9.02 | 8.90 | 8.74 | 8.50 |
| 5 | 12.13 | 12.06 | 12.01 | 11.94 | 11.81 | 11.62 | 11.40 | 11.39 | 12.04 | 12.92 | 12.46 | 12.29 | 12.05 | 11.68 |
| 6 | 14.95 | 15.10 | 15.23 | 15.32 | 15.26 | 15.10 | 14.86 | 14.84 | 15.67 | 16.85 | 16.24 | 16.03 | 15.72 | 15.26 |
| 7 | 17.61 | 17.97 | 18.35 | 18.64 | 18.74 | 18.67 | 18.49 | 18.49 | 19.54 | 21.02 | 20.28 | 20.00 | 19.60 | 18.98 |
| 8 | 19.85 | 20.54 | 21.18 | 21.74 | 22.08 | 22.25 | 22.22 | 22.26 | 23.55 | 25.40 | 24.56 | 24.24 | 23.75 | 22.98 |
| 9 | 21.92 | 22.91 | 23.80 | 24.58 | 25.07 | 25.35 | 25.45 | 25.65 | 27.21 | 29.49 | 28.76 | 28.46 | 28.02 | 27.17 |
| 10 | 23.84 | 25.16 | 26.34 | 27.36 | 28.04 | 28.45 | 28.64 | 28.89 | 30.66 | 33.25 | 32.45 | 32.11 | 31.62 | 30.80 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.02 | 7.83 | 7.70 | 7.61 | 7.50 | 7.38 | 7.25 | 7.29 | 7.69 | 8.28 | 8.03 | 7.94 | 7.81 | 7.62 |
| 5 | 10.56 | 10.40 | 10.32 | 10.26 | 10.15 | 10.00 | 9.82 | 9.85 | 10.42 | 11.22 | 10.87 | 10.75 | 10.56 | 10.27 |
| 6 | 13.04 | 13.05 | 13.07 | 13.09 | 12.99 | 12.85 | 12.65 | 12.66 | 13.38 | 14.40 | 13.91 | 13.73 | 13.49 | 13.12 |
| 7 | 15.44 | 15.64 | 15.82 | 15.97 | 15.97 | 15.86 | 15.66 | 15.65 | 16.54 | 17.80 | 17.17 | 16.94 | 16.61 | 16.09 |
| 8 | 17.70 | 18.07 | 18.46 | 18.78 | 18.91 | 18.89 | 18.73 | 18.74 | 19.81 | 21.35 | 20.62 | 20.33 | 19.92 | 19.26 |
| 9 | 19.64 | 20.30 | 20.90 | 21.45 | 21.78 | 21.95 | 21.88 | 21.92 | 23.19 | 25.03 | 24.21 | 23.89 | 23.41 | 22.62 |
| 10 | 21.45 | 22.36 | 23.18 | 23.91 | 24.38 | 24.63 | 24.72 | 24.90 | 26.40 | 28.61 | 27.88 | 27.51 | 26.97 | 26.08 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 32.445 | 27.877 |
| SC2 | 0 | 8 | 22.260 | 18.741 |
| SC3 | -18 | 7 | 18.703 | 15.982 |
| SC4 | -25 | 6 | 15.228 | 13.067 |
| SC5 | -34 | 6 | 15.003 | 13.065 |
| A | 1725 mm |
|---|---|
| B | 900 mm |
| C | 1350 mm |
| F | 860 mm |
| G | 1700 mm |
| E | 1335 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 1725 mm |
|---|---|
| Width | 1700 mm |
| Height | 1350 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.