EA-DI-280GE10-A01 C
53.87 kW
Defrost: None
Product code: EA-DI-263GE7-A13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 36,006 m³/h |
|---|---|
| External surface | 219.7 m² |
| Inner volume | 66.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 419 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 68.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | E |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø66,7 |
| EA-DI-263GE7-A13 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 23.27 | 22.90 | 22.67 | 22.56 | 22.37 | 22.14 | 21.90 | 21.94 | 23.21 | 25.03 | 24.36 | 24.11 | 23.75 | 23.22 |
| 5 | 30.16 | 30.00 | 29.95 | 29.92 | 29.77 | 29.51 | 29.19 | 29.16 | 30.85 | 33.26 | 32.31 | 31.96 | 31.46 | 30.72 |
| 6 | 36.82 | 37.11 | 37.40 | 37.69 | 37.68 | 37.47 | 37.11 | 37.04 | 39.17 | 42.23 | 40.94 | 40.47 | 39.78 | 38.72 |
| 7 | 43.18 | 44.06 | 44.68 | 45.38 | 45.67 | 45.64 | 45.39 | 45.34 | 47.95 | 51.73 | 50.14 | 49.54 | 48.67 | 47.28 |
| 8 | 48.71 | 50.17 | 51.55 | 52.82 | 53.63 | 54.00 | 53.90 | 53.94 | 57.08 | 61.65 | 59.84 | 59.13 | 58.08 | 56.40 |
| 9 | 53.81 | 55.92 | 57.85 | 59.59 | 60.72 | 61.39 | 61.72 | 62.10 | 65.88 | 71.42 | 69.77 | 69.01 | 67.81 | 65.85 |
| 10 | 58.57 | 61.41 | 63.98 | 66.25 | 67.76 | 68.70 | 69.21 | 69.72 | 73.99 | 80.23 | 78.43 | 77.68 | 76.56 | 74.68 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 20.29 | 19.90 | 19.69 | 19.61 | 19.47 | 19.30 | 19.13 | 19.24 | 20.39 | 22.04 | 21.51 | 21.30 | 21.02 | 20.59 |
| 5 | 26.20 | 25.85 | 25.74 | 25.73 | 25.60 | 25.40 | 25.14 | 25.20 | 26.69 | 28.82 | 28.04 | 27.76 | 27.37 | 26.77 |
| 6 | 32.02 | 31.99 | 32.06 | 32.20 | 32.11 | 31.92 | 31.63 | 31.64 | 33.48 | 36.13 | 35.07 | 34.68 | 34.12 | 33.27 |
| 7 | 37.67 | 38.02 | 38.41 | 38.80 | 38.89 | 38.76 | 38.47 | 38.43 | 40.66 | 43.88 | 42.54 | 42.02 | 41.28 | 40.13 |
| 8 | 43.06 | 43.91 | 44.57 | 45.30 | 45.63 | 45.66 | 45.45 | 45.45 | 48.09 | 51.92 | 50.34 | 49.72 | 48.82 | 47.37 |
| 9 | 47.86 | 49.20 | 50.50 | 51.72 | 52.46 | 52.67 | 52.58 | 52.66 | 55.73 | 60.20 | 58.45 | 57.74 | 56.68 | 54.91 |
| 10 | 52.29 | 54.18 | 55.94 | 57.55 | 58.56 | 59.17 | 59.43 | 59.81 | 63.43 | 68.62 | 66.72 | 65.92 | 64.72 | 62.66 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 78.430 | 66.716 |
| SC2 | 0 | 8 | 53.937 | 45.452 |
| SC3 | -18 | 7 | 45.538 | 38.862 |
| SC4 | -25 | 6 | 37.403 | 32.064 |
| SC5 | -34 | 6 | 36.934 | 32.055 |
| A | 3025 mm |
|---|---|
| B | 1000 mm |
| C | 1150 mm |
| F | 960 mm |
| G | 1540 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø66,7 |
| Length | 3025 mm |
|---|---|
| Width | 1540 mm |
| Height | 1150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.