EA-DI-280GG4-A01 C
83.77 kW
Defrost: None
Product code: EA-DI-291GE4-A04 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 46,792 m³/h |
|---|---|
| External surface | 390.9 m² |
| Inner volume | 80.3 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 592 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 71.0 dB(A) |
|---|---|
| Sound power | 94.3 dB(A) |
| Energy class | E |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EA-DI-291GE4-A04 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 36.42 | 36.44 | 36.52 | 36.57 | 36.44 | 36.13 | 35.71 | 36.45 | 38.79 | 42.01 | 40.99 | 40.61 | 40.07 | 39.26 |
| 5 | 46.26 | 47.05 | 47.71 | 48.24 | 48.28 | 47.97 | 47.32 | 47.91 | 50.87 | 55.02 | 53.51 | 53.00 | 52.30 | 51.28 |
| 6 | 55.28 | 57.00 | 58.57 | 59.88 | 60.40 | 60.34 | 59.81 | 60.35 | 63.96 | 69.09 | 66.94 | 66.15 | 65.02 | 63.28 |
| 7 | 63.04 | 65.70 | 68.08 | 70.15 | 71.38 | 71.95 | 71.97 | 72.79 | 77.26 | 83.77 | 81.39 | 80.36 | 78.84 | 76.42 |
| 8 | 70.23 | 73.97 | 77.32 | 80.19 | 81.99 | 82.92 | 83.13 | 84.01 | 89.14 | 96.66 | 94.08 | 93.05 | 91.51 | 88.97 |
| 9 | 76.84 | 81.78 | 86.21 | 90.00 | 92.50 | 93.89 | 94.34 | 95.37 | 101.19 | 109.71 | 106.81 | 105.59 | 103.75 | 100.69 |
| 10 | 82.87 | 89.09 | 94.71 | 99.56 | 102.79 | 104.74 | 105.57 | 106.82 | 113.36 | 122.89 | 119.73 | 118.33 | 116.21 | 112.62 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 29.99 | 31.98 | 34.72 | 34.06 | 33.85 | 33.59 | 33.14 |
| 5 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 41.00 | 44.39 | 43.20 | 42.79 | 42.24 | 41.49 |
| 6 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 7 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 8 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 9 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 10 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 119.727 | — |
| SC2 | 0 | 8 | 84.007 | — |
| SC3 | -18 | 7 | 70.729 | — |
| SC4 | -25 | 6 | 58.573 | — |
| SC5 | -34 | 6 | 55.729 | — |
| A | 3025 mm |
|---|---|
| B | 1000 mm |
| C | 1350 mm |
| F | 960 mm |
| G | 1800 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 3025 mm |
|---|---|
| Width | 1800 mm |
| Height | 1350 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.