EA-DI-363GG7-A08 C
86.40 kW
Defrost: None
Product code: EA-DI-291GI10-A04 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 45,144 m³/h |
|---|---|
| External surface | 317.4 m² |
| Inner volume | 131.9 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 699 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 71.0 dB(A) |
|---|---|
| Sound power | 94.7 dB(A) |
| Energy class | D |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø80 |
| EA-DI-291GI10-A04 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 37.09 | 37.06 | 37.10 | 37.15 | 36.91 | 36.47 | 35.87 | 36.48 | 38.75 | 41.86 | 40.76 | 40.39 | 39.81 | 38.82 |
| 5 | 47.20 | 47.84 | 48.40 | 48.85 | 48.76 | 48.38 | 47.69 | 48.19 | 51.08 | 55.13 | 53.36 | 52.74 | 51.88 | 50.61 |
| 6 | 56.60 | 58.17 | 59.53 | 60.63 | 61.02 | 60.83 | 60.05 | 60.43 | 63.98 | 69.06 | 66.70 | 65.80 | 64.49 | 62.43 |
| 7 | 65.32 | 67.65 | 69.97 | 71.92 | 72.92 | 73.15 | 72.71 | 73.12 | 77.40 | 83.61 | 80.74 | 79.60 | 77.87 | 75.03 |
| 8 | 72.73 | 76.36 | 79.65 | 82.50 | 84.29 | 85.20 | 85.32 | 85.99 | 91.05 | 98.42 | 95.19 | 93.82 | 91.72 | 88.21 |
| 9 | 79.61 | 84.41 | 88.74 | 92.48 | 94.88 | 96.23 | 96.66 | 97.68 | 103.59 | 112.21 | 109.15 | 107.75 | 105.62 | 101.60 |
| 10 | 85.92 | 91.95 | 97.43 | 102.19 | 105.33 | 107.22 | 107.98 | 109.24 | 115.87 | 125.51 | 122.19 | 120.61 | 118.19 | not rated |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 32.89 | 32.63 | 32.31 | 31.88 |
| 5 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 6 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 7 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 8 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 9 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 10 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 122.185 | — |
| SC2 | 0 | 8 | 85.994 | — |
| SC3 | -18 | 7 | 72.417 | — |
| SC4 | -25 | 6 | 59.534 | — |
| SC5 | -34 | 6 | 57.022 | — |
| A | 3025 mm |
|---|---|
| B | 1200 mm |
| C | 1350 mm |
| F | 1160 mm |
| G | 2000 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø80 |
| Length | 3025 mm |
|---|---|
| Width | 2000 mm |
| Height | 1350 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.