EA-DI-363GI4-A13 C
123.33 kW
Defrost: None
Product code: EA-DI-391GI10-A04 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 67,734 m³/h |
|---|---|
| External surface | 476.1 m² |
| Inner volume | 192.0 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 1,032 kg |
| Quantity | 3 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 8,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 73.0 dB(A) |
|---|---|
| Sound power | 96.7 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø66,7 |
| EA-DI-391GI10-A04 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 52.87 | 52.97 | 53.33 | 53.61 | 53.41 | 52.86 | 52.05 | 52.95 | 56.26 | 60.78 | 59.16 | 58.63 | 57.76 | 56.30 |
| 5 | 66.54 | 68.06 | 69.36 | 70.37 | 70.60 | 70.14 | 69.26 | 70.05 | 74.27 | 80.20 | 77.65 | 76.76 | 75.49 | 73.62 |
| 6 | 79.28 | 82.33 | 84.96 | 86.65 | 87.67 | 87.78 | 87.10 | 87.83 | 93.04 | 100.51 | 97.12 | 95.84 | 93.96 | 90.96 |
| 7 | 90.96 | 95.04 | 99.09 | 102.60 | 104.77 | 105.55 | 105.27 | 106.13 | 112.43 | 121.60 | 117.61 | 116.01 | 113.61 | 109.55 |
| 8 | 100.49 | 106.58 | 112.09 | 116.84 | 119.98 | 121.73 | 122.30 | 123.68 | 131.25 | 142.34 | 138.51 | 136.63 | 133.70 | 128.75 |
| 9 | 109.55 | 117.37 | 124.49 | 130.68 | 134.81 | 137.32 | 138.37 | 140.13 | 148.72 | 161.26 | 157.09 | 155.16 | 152.21 | 147.09 |
| 10 | ≈ 117.78 | 127.42 | 136.28 | 144.04 | 149.36 | 152.77 | 154.40 | 156.59 | 166.25 | 180.29 | 175.79 | 173.63 | 170.29 | not rated |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 47.73 | 47.34 | 46.88 | 46.22 |
| 5 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 6 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 7 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 8 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 9 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 10 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 175.794 | — |
| SC2 | 0 | 8 | 123.684 | — |
| SC3 | -18 | 7 | 103.625 | — |
| SC4 | -25 | 6 | 84.960 | — |
| SC5 | -34 | 6 | 80.044 | — |
| A | 4325 mm |
|---|---|
| B | 1200 mm |
| C | 1350 mm |
| F | 1160 mm |
| G | 2000 mm |
| E1 | 1318 mm |
| E2 | 1300 mm |
| E | 3935 mm |
| D IN | 2 x Ø35 |
| D OUT | 2 x Ø66,7 |
| Length | 4325 mm |
|---|---|
| Width | 2000 mm |
| Height | 1350 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.