EA-DI-491GG7-A04 C
160.68 kW
Defrost: None
Product code: EA-DI-491GE4-A04 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 93,583 m³/h |
|---|---|
| External surface | 781.9 m² |
| Inner volume | 157.9 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 1,184 kg |
| Quantity | 4 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 11,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 73.0 dB(A) |
|---|---|
| Sound power | 97.3 dB(A) |
| Energy class | E |
| Inlet | Ø54 |
|---|---|
| Outlet | Ø80 |
| EA-DI-491GE4-A04 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 66.09 | 68.21 | 69.97 | 71.31 | 71.79 | 71.40 | 70.82 | 72.34 | 77.04 | 83.47 | 81.64 | 80.85 | 79.72 | 77.98 |
| 5 | 81.11 | 85.25 | 88.81 | 91.88 | 93.75 | 94.32 | 93.97 | 95.58 | 101.58 | 110.03 | 107.09 | 106.06 | 104.60 | 102.48 |
| 6 | 93.93 | 99.89 | 105.25 | 109.86 | 112.90 | 114.62 | 115.28 | 117.30 | 124.77 | 135.55 | 132.54 | 131.37 | 129.63 | 126.85 |
| 7 | ≈ 105.40 | 113.51 | 120.92 | 127.34 | 131.76 | 134.46 | 135.71 | 138.02 | 146.78 | 159.52 | 155.87 | 154.39 | 152.15 | 148.47 |
| 8 | ≈ 115.69 | 126.08 | 135.72 | 144.18 | 150.22 | 154.14 | 156.17 | 158.91 | 169.02 | 183.82 | 179.61 | 177.86 | 175.15 | 170.57 |
| 9 | ≈ 124.89 | 137.60 | 149.61 | 160.28 | 168.18 | 173.50 | 176.49 | 179.85 | 191.36 | 208.22 | 203.69 | 201.66 | 198.52 | 193.09 |
| 10 | ≈ 88.01 | ≈ 148.08 | 162.51 | 175.56 | 185.39 | 192.33 | 196.56 | 200.75 | 213.71 | 232.65 | 227.95 | 225.69 | 222.16 | 215.91 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 58.96 | 62.89 | 68.26 | 66.86 | 66.43 | 65.86 | 65.07 |
| 5 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 81.07 | 87.79 | 85.38 | 84.54 | 83.35 | 81.61 |
| 6 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 7 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 8 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 9 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 10 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 227.950 | — |
| SC2 | 0 | 8 | 158.912 | — |
| SC3 | -18 | 7 | 129.326 | — |
| SC4 | -25 | 6 | 105.254 | — |
| SC5 | -34 | 6 | 95.311 | — |
| A | 5625 mm |
|---|---|
| B | 1000 mm |
| C | 1350 mm |
| F | 960 mm |
| G | 1800 mm |
| E1 | 1318 mm |
| E2 | 1300 mm |
| E | 5235 mm |
| D IN | 1 x Ø54 |
| D OUT | 1 x Ø80 |
| Length | 5625 mm |
|---|---|
| Width | 1800 mm |
| Height | 1350 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.