Skip to Content

Unit cooler EA-DR-350BB8-A10 C

Unit cooler EA-DR-350BB8-A10 C
Illustrative photo

Producer: Karyer · Line: EA-DR (Banana Ripnening)

Product code: EA-DR-350BB8-A10 C

Cooling capacity i
16.79 kW
Air flow
23,414 m³/h
Fin spacing
8.0 mm
Air throw
24 m
Fans
3 × ⌀500 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Data

Evaporator
Air flow 23,414 m³/h
Air throw 24 m
External surface 58.6 m²
Inner volume 18.9 dm³
Fin spacing 8.0 mm
Fin materialAluminium
Net weight 154 kg
Fans
Quantity 3
Diameter 500 mm
Speed 1,360 rpm
Power 2,070 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 63.0 dB(A)
Sound power 85.7 dB(A)
Energy class E
Connections
Inlet Ø22
Outlet Ø35
Defrost
EA-DR-350BB8-A10 C None

Performance

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

High speed (Δ)
16.786 kW
Low speed (Y)
15.205 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

High speed (Δ)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 6.95 6.91 6.86 6.83 6.76 6.67 6.56 6.54 6.90 7.41 7.17 7.08 6.95 6.77
5 8.97 9.09 9.18 9.24 9.22 9.13 9.01 8.99 9.50 10.22 9.88 9.76 9.57 9.29
6 10.88 11.14 11.43 11.65 11.74 11.73 11.64 11.64 12.31 13.26 12.83 12.67 12.44 12.08
7 12.46 12.98 13.45 13.86 14.12 14.27 14.33 14.42 15.27 16.49 15.99 15.80 15.52 15.07
8 13.91 14.65 15.32 15.89 16.28 16.51 16.63 16.79 17.82 19.33 18.90 18.72 18.46 18.04
9 15.24 16.22 17.11 17.88 18.42 18.76 18.95 19.15 20.35 22.09 21.61 21.42 21.12 20.63
10 16.45 17.70 18.83 19.81 20.51 20.99 21.27 21.53 22.89 24.87 24.36 24.14 23.82 23.27

Low speed (Y)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 6.32 6.26 6.22 6.19 6.13 6.05 5.97 5.98 6.31 6.79 6.59 6.51 6.41 6.24
5 8.20 8.25 8.29 8.32 8.28 8.20 8.09 8.11 8.57 9.23 8.95 8.84 8.70 8.46
6 9.98 10.20 10.38 10.49 10.53 10.49 10.39 10.41 11.01 11.86 11.48 11.35 11.15 10.84
7 11.58 11.98 12.34 12.66 12.82 12.85 12.80 12.83 13.58 14.66 14.20 14.03 13.77 13.37
8 12.97 13.55 14.07 14.53 14.83 15.00 15.07 15.21 16.14 17.50 17.05 16.85 16.55 16.06
9 14.26 15.05 15.75 16.37 16.78 17.04 17.17 17.33 18.40 19.97 19.51 19.33 19.05 18.59
10 15.45 16.45 17.37 18.16 18.71 19.07 19.26 19.47 20.68 22.46 21.96 21.75 21.44 20.92

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] High speed (Δ) [kW]Low speed (Y) [kW]
SC1 10 10 24.35821.963
SC2 0 8 16.78615.205
SC3 -18 7 13.97712.739
SC4 -25 6 11.42810.379
SC5 -34 6 10.96510.045

Dimensions

Dimension drawing of EA-DR-350BB8-A10 C
Dimension drawing
Dimensions as drawn
A 2637 mm
B 740 mm
C 775 mm
F 660 mm
E1 768 mm
E2 750 mm
E 2285 mm
D IN 1 x Ø22
D OUT 1 x Ø35
Overall [mm]
Length 2637 mm
Width 740 mm
Height 775 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.