EA-DV-191GC4-A04 C
31.43 kW
Defrost: None
Product code: EA-DV-163GG10-A13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 17,729 m³/h |
|---|---|
| External surface | 105.5 m² |
| Inner volume | 43.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 286 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 65.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EA-DV-163GG10-A13 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 13.35 | 13.09 | 12.92 | 12.81 | 12.67 | 12.50 | 12.32 | 12.32 | 13.03 | 14.05 | 13.63 | 13.48 | 13.26 | 12.93 |
| 5 | 17.31 | 17.11 | 17.04 | 17.00 | 16.88 | 16.70 | 16.47 | 16.42 | 17.36 | 18.69 | 18.10 | 17.89 | 17.59 | 17.13 |
| 6 | 21.14 | 21.20 | 21.29 | 21.39 | 21.32 | 21.16 | 20.93 | 20.85 | 22.03 | 23.73 | 22.95 | 22.65 | 22.24 | 21.59 |
| 7 | 24.82 | 25.17 | 25.51 | 25.81 | 25.89 | 25.80 | 25.59 | 25.51 | 26.95 | 29.02 | 28.08 | 27.71 | 27.18 | 26.33 |
| 8 | 28.29 | 29.00 | 29.54 | 30.11 | 30.38 | 30.43 | 30.31 | 30.27 | 32.00 | 34.53 | 33.43 | 33.00 | 32.36 | 31.33 |
| 9 | 31.32 | 32.38 | 33.37 | 34.27 | 34.84 | 35.10 | 35.08 | 35.12 | 37.16 | 40.13 | 38.94 | 38.45 | 37.72 | 36.52 |
| 10 | 34.14 | 35.59 | 36.91 | 38.10 | 38.85 | 39.32 | 39.54 | 39.79 | 42.19 | 45.71 | 44.52 | 43.98 | 43.17 | 41.82 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.43 | 11.17 | 11.02 | 10.94 | 10.84 | 10.72 | 10.59 | 10.63 | 11.27 | 12.17 | 11.85 | 11.74 | 11.58 | 11.32 |
| 5 | 14.72 | 14.52 | 14.41 | 14.37 | 14.27 | 14.12 | 13.94 | 13.95 | 14.76 | 15.93 | 15.45 | 15.28 | 15.04 | 14.69 |
| 6 | 18.06 | 17.95 | 17.91 | 17.94 | 17.88 | 17.73 | 17.53 | 17.51 | 18.51 | 19.96 | 19.32 | 19.09 | 18.75 | 18.23 |
| 7 | 21.26 | 21.33 | 21.46 | 21.61 | 21.61 | 21.48 | 21.28 | 21.24 | 22.45 | 24.21 | 23.42 | 23.11 | 22.65 | 21.93 |
| 8 | 24.33 | 24.65 | 24.97 | 25.28 | 25.38 | 25.33 | 25.15 | 25.10 | 26.53 | 28.61 | 27.66 | 27.28 | 26.72 | 25.79 |
| 9 | 27.25 | 27.85 | 28.42 | 28.85 | 29.09 | 29.14 | 29.02 | 29.01 | 30.68 | 33.09 | 32.02 | 31.58 | 30.92 | 29.83 |
| 10 | 30.00 | 30.82 | 31.67 | 32.42 | 32.82 | 32.99 | 32.94 | 32.98 | 34.89 | 37.65 | 36.49 | 35.99 | 35.24 | 33.98 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 44.515 | 36.486 |
| SC2 | 0 | 8 | 30.266 | 25.095 |
| SC3 | -18 | 7 | 25.864 | 21.627 |
| SC4 | -25 | 6 | 21.290 | 17.905 |
| SC5 | -34 | 6 | 21.186 | 18.057 |
| A | 1725 mm |
|---|---|
| B | 1100 mm |
| C | 1260 mm |
| F | 1060 mm |
| G | 1785 mm |
| E | 1335 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 1725 mm |
|---|---|
| Width | 1785 mm |
| Height | 1260 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.