EA-DV-263GC10-A08 C
32.05 kW
Defrost: None
Product code: EA-DV-191GE10-A04 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 26,358 m³/h |
|---|---|
| External surface | 95.2 m² |
| Inner volume | 40.8 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 366 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 67.0 dB(A) |
|---|---|
| Sound power | 90.3 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EA-DV-191GE10-A04 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 13.66 | 13.41 | 13.24 | 13.11 | 12.92 | 12.70 | 12.46 | 12.54 | 13.22 | 14.22 | 13.76 | 13.59 | 13.36 | 13.00 |
| 5 | 17.85 | 17.78 | 17.73 | 17.66 | 17.50 | 17.25 | 16.94 | 17.01 | 17.99 | 19.35 | 18.71 | 18.49 | 18.17 | 17.69 |
| 6 | 21.87 | 22.10 | 22.30 | 22.45 | 22.39 | 22.17 | 21.83 | 21.86 | 23.12 | 24.87 | 24.00 | 23.68 | 23.24 | 22.56 |
| 7 | 25.68 | 26.30 | 26.72 | 27.15 | 27.29 | 27.20 | 26.92 | 26.95 | 28.49 | 30.69 | 29.60 | 29.19 | 28.59 | 27.65 |
| 8 | 28.99 | 29.97 | 30.87 | 31.68 | 32.15 | 32.31 | 32.13 | 32.21 | 34.07 | 36.75 | 35.51 | 35.02 | 34.29 | 33.11 |
| 9 | 31.99 | 33.39 | 34.66 | 35.76 | 36.45 | 36.81 | 36.91 | 37.19 | 39.43 | 42.73 | 41.57 | 41.01 | 40.17 | 38.79 |
| 10 | 34.79 | 36.65 | 38.32 | 39.77 | 40.71 | 41.25 | 41.45 | 41.79 | 44.33 | 48.04 | 46.80 | 46.28 | 45.49 | 44.17 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.62 | 11.37 | 11.21 | 11.10 | 10.96 | 10.80 | 10.63 | 10.77 | 11.41 | 12.30 | 11.96 | 11.83 | 11.65 | 11.38 |
| 5 | 15.10 | 14.93 | 14.84 | 14.78 | 14.64 | 14.44 | 14.20 | 14.30 | 15.15 | 16.33 | 15.84 | 15.67 | 15.43 | 15.08 |
| 6 | 18.61 | 18.60 | 18.63 | 18.67 | 18.55 | 18.35 | 18.06 | 18.13 | 19.17 | 20.65 | 19.95 | 19.70 | 19.35 | 18.81 |
| 7 | 21.95 | 22.18 | 22.41 | 22.61 | 22.61 | 22.45 | 22.14 | 22.17 | 23.43 | 25.25 | 24.35 | 24.01 | 23.51 | 22.71 |
| 8 | 25.13 | 25.67 | 26.16 | 26.49 | 26.64 | 26.57 | 26.31 | 26.34 | 27.84 | 30.02 | 28.91 | 28.46 | 27.81 | 26.73 |
| 9 | 28.09 | 28.85 | 29.65 | 30.37 | 30.70 | 30.76 | 30.57 | 30.61 | 32.37 | 34.91 | 33.65 | 33.12 | 32.34 | 31.04 |
| 10 | 30.59 | 31.77 | 32.86 | 33.83 | 34.39 | 34.69 | 34.72 | 34.94 | 36.95 | 39.86 | 38.48 | 37.88 | 36.96 | 35.48 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 46.803 | 38.481 |
| SC2 | 0 | 8 | 32.205 | 26.339 |
| SC3 | -18 | 7 | 27.241 | 22.632 |
| SC4 | -25 | 6 | 22.298 | 18.626 |
| SC5 | -34 | 6 | 21.954 | 18.633 |
| A | 1725 mm |
|---|---|
| B | 1000 mm |
| C | 1460 mm |
| F | 960 mm |
| G | 1875 mm |
| E | 1335 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 1725 mm |
|---|---|
| Width | 1875 mm |
| Height | 1460 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.