EA-DV-263GI10-A08 C
65.98 kW
Defrost: None
Product code: EA-DV-263GE4-A13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 34,889 m³/h |
|---|---|
| External surface | 325.8 m² |
| Inner volume | 66.6 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 503 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 68.0 dB(A) |
|---|---|
| Sound power | 90.9 dB(A) |
| Energy class | E |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø66,7 |
| EA-DV-263GE4-A13 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 29.08 | 29.01 | 28.98 | 29.07 | 29.01 | 28.84 | 28.61 | 28.79 | 30.52 | 33.01 | 32.22 | 31.95 | 31.52 | 30.87 |
| 5 | 36.87 | 37.34 | 37.76 | 38.14 | 38.21 | 38.06 | 37.76 | 37.87 | 40.11 | 43.30 | 42.13 | 41.71 | 41.11 | 40.21 |
| 6 | 44.30 | 45.28 | 46.34 | 47.23 | 47.64 | 47.70 | 47.48 | 47.59 | 50.39 | 54.43 | 52.88 | 52.28 | 51.43 | 50.11 |
| 7 | 50.52 | 52.41 | 54.13 | 55.68 | 56.65 | 57.20 | 57.42 | 57.79 | 61.21 | 66.17 | 64.29 | 63.56 | 62.48 | 60.76 |
| 8 | 56.34 | 59.04 | 61.48 | 63.62 | 65.02 | 65.85 | 66.25 | 66.76 | 70.84 | 76.83 | 75.04 | 74.33 | 73.25 | 71.49 |
| 9 | 61.71 | 65.33 | 68.58 | 71.41 | 73.33 | 74.49 | 75.12 | 75.78 | 80.43 | 87.24 | 85.26 | 84.43 | 83.19 | 81.11 |
| 10 | 66.64 | 71.23 | 75.38 | 79.00 | 81.49 | 83.10 | 84.01 | 84.86 | 90.10 | 97.76 | 95.61 | 94.68 | 93.28 | 90.90 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 24.89 | 24.72 | 24.68 | 24.74 | 24.69 | 24.56 | 24.37 | 24.67 | 26.19 | 28.37 | 27.75 | 27.53 | 27.23 | 26.78 |
| 5 | 31.66 | 31.74 | 31.91 | 32.11 | 32.08 | 31.93 | 31.67 | 31.92 | 33.85 | 36.62 | 35.67 | 35.33 | 34.85 | 34.13 |
| 6 | 38.15 | 38.70 | 39.23 | 39.73 | 39.87 | 39.77 | 39.47 | 39.59 | 41.94 | 45.34 | 44.03 | 43.54 | 42.83 | 41.73 |
| 7 | 44.32 | 45.29 | 46.34 | 47.25 | 47.68 | 47.74 | 47.50 | 47.66 | 50.46 | 54.54 | 52.89 | 52.23 | 51.29 | 49.78 |
| 8 | 49.62 | 51.35 | 52.95 | 54.40 | 55.29 | 55.75 | 55.75 | 55.97 | 59.26 | 64.05 | 62.13 | 61.34 | 60.18 | 58.28 |
| 9 | 54.60 | 57.01 | 59.19 | 61.13 | 62.36 | 63.01 | 63.23 | 63.71 | 67.56 | 73.18 | 71.34 | 70.55 | 69.31 | 67.04 |
| 10 | 59.24 | 62.40 | 65.25 | 67.74 | 69.33 | 70.28 | 70.66 | 71.23 | 75.54 | 81.82 | 79.79 | 78.89 | 77.53 | 75.24 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 95.612 | 79.788 |
| SC2 | 0 | 8 | 66.756 | 55.970 |
| SC3 | -18 | 7 | 56.122 | 47.474 |
| SC4 | -25 | 6 | 46.341 | 39.232 |
| SC5 | -34 | 6 | 44.629 | 38.317 |
| A | 3025 mm |
|---|---|
| B | 1000 mm |
| C | 1260 mm |
| F | 960 mm |
| G | 1685 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø66,7 |
| Length | 3025 mm |
|---|---|
| Width | 1685 mm |
| Height | 1260 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.