EA-130AC7-C05 C
1.76 kW
Defrost: None
Product code: EA-130AC8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 1,337 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 5.9 m² |
| Inner volume | 2.3 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 22 kg |
| Quantity | 1 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 62 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 64.1 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø12,7 |
| EA-130AC8-C01 C | None |
|---|---|
| EA-130AC8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.70 | 0.70 | 0.71 | 0.72 | 0.72 | 0.71 | 0.70 | 0.71 | 0.76 | 0.81 | 0.79 | 0.78 | 0.77 | 0.75 |
| 5 | 0.88 | 0.91 | 0.94 | 0.95 | 0.96 | 0.96 | 0.96 | 0.96 | 1.02 | 1.11 | 1.07 | 1.06 | 1.05 | 1.02 |
| 6 | 1.07 | 1.12 | 1.16 | 1.20 | 1.22 | 1.23 | 1.22 | 1.24 | 1.31 | 1.42 | 1.38 | 1.36 | 1.34 | 1.30 |
| 7 | 1.24 | 1.31 | 1.38 | 1.44 | 1.48 | 1.50 | 1.50 | 1.52 | 1.61 | 1.74 | 1.70 | 1.68 | 1.65 | 1.60 |
| 8 | 1.38 | 1.48 | 1.57 | 1.65 | 1.70 | 1.73 | 1.75 | 1.78 | 1.90 | 2.06 | 2.02 | 2.00 | 1.97 | 1.92 |
| 9 | 1.51 | 1.63 | 1.75 | 1.83 | 1.91 | 1.96 | 1.99 | 2.03 | 2.16 | 2.35 | 2.30 | 2.28 | 2.25 | 2.20 |
| 10 | ≈ 1.62 | 1.77 | 1.90 | 2.02 | 2.12 | 2.18 | 2.23 | 2.27 | 2.42 | 2.63 | 2.59 | 2.57 | 2.53 | 2.48 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 2.589 |
| SC2 | 0 | 8 | 1.783 |
| SC3 | -18 | 7 | 1.454 |
| SC4 | -25 | 6 | 1.162 |
| SC5 | -34 | 6 | 1.082 |
| A | 777 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E | 455 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø12,7 |
| Length | 777 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.