EA-130AC4-C01 C
2.35 kW
Defrost: None
Product code: EA-130BE10-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,236 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 9.6 m² |
| Inner volume | 4.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 25 kg |
| Quantity | 1 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 120 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 41.0 dB(A) |
|---|---|
| Sound power | 62.0 dB(A) |
| Energy class | C |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| EA-130BE10-C05 C | None |
|---|---|
| EA-130BE10-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.02 | 1.02 | 1.01 | 1.02 | 1.01 | 1.00 | 0.99 | 1.01 | 1.07 | 1.16 | 1.13 | 1.12 | 1.10 | 1.08 |
| 5 | 1.31 | 1.31 | 1.32 | 1.33 | 1.33 | 1.32 | 1.31 | 1.32 | 1.40 | 1.52 | 1.47 | 1.46 | 1.44 | 1.40 |
| 6 | 1.58 | 1.60 | 1.63 | 1.65 | 1.66 | 1.66 | 1.65 | 1.66 | 1.76 | 1.90 | 1.84 | 1.82 | 1.79 | 1.74 |
| 7 | 1.85 | 1.89 | 1.94 | 1.98 | 2.00 | 2.00 | 2.00 | 2.01 | 2.13 | 2.30 | 2.23 | 2.20 | 2.16 | 2.09 |
| 8 | 2.11 | 2.18 | 2.24 | 2.30 | 2.34 | 2.35 | 2.35 | 2.36 | 2.50 | 2.71 | 2.63 | 2.59 | 2.54 | 2.46 |
| 9 | 2.35 | 2.45 | 2.54 | 2.62 | 2.67 | 2.70 | 2.70 | 2.73 | 2.89 | 3.12 | 3.04 | 3.00 | 2.94 | 2.84 |
| 10 | 2.57 | 2.70 | 2.82 | 2.93 | 3.00 | 3.05 | 3.06 | 3.09 | 3.28 | 3.54 | 3.45 | 3.41 | 3.34 | 3.23 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 3.451 |
| SC2 | 0 | 8 | 2.364 |
| SC3 | -18 | 7 | 1.987 |
| SC4 | -25 | 6 | 1.628 |
| SC5 | -34 | 6 | 1.589 |
| A | 907 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E | 585 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 907 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.