EA-230AC4-C05 C
4.25 kW
Defrost: None
Product code: EA-135AG10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 2,088 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 14.0 m² |
| Inner volume | 6.5 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 41 kg |
| Quantity | 1 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 165 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-135AG10-C01 C | None |
|---|---|
| EA-135AG10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.80 | 1.80 | 1.80 | 1.81 | 1.80 | 1.78 | 1.75 | 1.78 | 1.90 | 2.05 | 2.00 | 1.98 | 1.96 | 1.92 |
| 5 | 2.29 | 2.32 | 2.35 | 2.38 | 2.38 | 2.37 | 2.33 | 2.36 | 2.51 | 2.71 | 2.62 | 2.59 | 2.55 | 2.49 |
| 6 | 2.76 | 2.83 | 2.90 | 2.96 | 2.98 | 2.98 | 2.95 | 2.97 | 3.15 | 3.40 | 3.29 | 3.24 | 3.18 | 3.07 |
| 7 | 3.22 | 3.34 | 3.44 | 3.53 | 3.59 | 3.60 | 3.58 | 3.61 | 3.82 | 4.13 | 3.98 | 3.93 | 3.84 | 3.70 |
| 8 | 3.64 | 3.81 | 3.97 | 4.11 | 4.20 | 4.22 | 4.22 | 4.25 | 4.50 | 4.86 | 4.71 | 4.64 | 4.54 | 4.35 |
| 9 | 4.02 | 4.25 | 4.46 | 4.65 | 4.77 | 4.84 | 4.86 | 4.90 | 5.18 | 5.60 | 5.43 | 5.36 | 5.24 | 5.02 |
| 10 | 4.35 | 4.64 | 4.91 | 5.14 | 5.28 | 5.38 | 5.42 | 5.50 | 5.83 | 6.32 | 6.16 | 6.09 | 5.95 | 5.70 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.162 |
| SC2 | 0 | 8 | 4.250 |
| SC3 | -18 | 7 | 3.559 |
| SC4 | -25 | 6 | 2.899 |
| SC5 | -34 | 6 | 2.778 |
| A | 857 mm |
|---|---|
| B | 673 mm |
| C | 525 mm |
| F | 495 mm |
| E | 535 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 857 mm |
|---|---|
| Width | 623 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.