EA-135AG4-C01 C
4.89 kW
Defrost: None
Product code: EA-140AE10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,042 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 13.4 m² |
| Inner volume | 6.2 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 41 kg |
| Quantity | 1 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 160 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-140AE10-C01 C | None |
|---|---|
| EA-140AE10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.98 | 1.98 | 1.98 | 1.98 | 1.97 | 1.95 | 1.91 | 1.94 | 2.06 | 2.22 | 2.15 | 2.13 | 2.09 | 2.03 |
| 5 | 2.54 | 2.58 | 2.62 | 2.65 | 2.65 | 2.64 | 2.60 | 2.63 | 2.79 | 3.01 | 2.91 | 2.88 | 2.83 | 2.77 |
| 6 | 3.07 | 3.17 | 3.26 | 3.33 | 3.36 | 3.36 | 3.33 | 3.36 | 3.56 | 3.85 | 3.72 | 3.67 | 3.60 | 3.49 |
| 7 | 3.59 | 3.75 | 3.89 | 4.01 | 4.08 | 4.10 | 4.08 | 4.12 | 4.36 | 4.72 | 4.56 | 4.50 | 4.41 | 4.26 |
| 8 | 4.05 | 4.27 | 4.47 | 4.65 | 4.76 | 4.83 | 4.85 | 4.88 | 5.17 | 5.60 | 5.43 | 5.36 | 5.25 | 5.07 |
| 9 | 4.45 | 4.73 | 4.99 | 5.22 | 5.35 | 5.46 | 5.50 | 5.58 | 5.93 | 6.44 | 6.28 | 6.21 | 6.10 | 5.90 |
| 10 | 4.81 | 5.17 | 5.46 | 5.75 | 5.95 | 6.09 | 6.16 | 6.26 | 6.65 | 7.22 | 7.06 | 6.98 | 6.86 | 6.65 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 7.056 |
| SC2 | 0 | 8 | 4.878 |
| SC3 | -18 | 7 | 4.043 |
| SC4 | -25 | 6 | 3.255 |
| SC5 | -34 | 6 | 3.096 |
| A | 917 mm |
|---|---|
| B | 636 mm |
| C | 605 mm |
| F | 445 mm |
| E | 585 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 917 mm |
|---|---|
| Width | 636 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.